1
ASTRA-BPA
Addressable relay unit
User Guide
This operating manual is intended to study the principle of operation,
proper use, storage and maintenance of the Astra-BPA addressable
relay unit.
The manufacturer reserves the right to make changes to the design,
software, circuit solutions and product packaging that do not worsen its
technical characteristics, do not violate mandatory regulatory require-
ments, without prior notice to the consumer.
The technical features of the product not specified in the instruction
manual in terms of design, software and circuit solutions are standard
for the product, if they do not worsen the declared technical character-
istics.
Abbreviations
:
SLC
–
Signaling Line Circuit;
Addressable devices
– Astra-42A smoke fire detectors, Astra-43A heat
fire detectors, Astra-45A manual fire manual call point, Astra-BRA relay
unit, Astra-MA addressable mark;
BPA
– Addressable relay unit;
Tutorial
– tutorial built into the PKM Astra Pro Configuration Module, or
Astra-812 Pro Configuration Instructions from the keypad (available on the
website www.teko.biz);
Control Panel
–
fire alarm Control Panel "Astra-812 Pro or Astra-8945
Pro with firmware version v5_5 and higher;
PKM
Astra Pro
– Astra Pro control/configuration software package
(see on the website www.teko.biz);
FW
–
Firmware;
RPA
– extender wired address Astra-A RPA with software version
v5_5 and higher;
LP
– Laser Pointer Astra-942;
AL
– Alarm loop (wired zone)
1 FUNCTION
1.1
BPA is designed for:
– control the communication line and managing devices of the alerting
system and control evacuation of people in case of fire;
– control and start of automation control cabinets (signals "Failure",
"Emergency", "Automatics disabled" and " smoke exhaust Fan (pump,
lock) activated);
– control and service fire automatics powered by 12 V or 24 V;
– transmission of signals through an intermediate relay device to the in-
puts of elevator controllers, voice alerting units, etc.);
– control through the built-in two AL (Zone 1 – Zone 4) of addressable
fire detectors, intrusion, technological devices (including those powered by
AL) and transmission of notifications via SLC through RPA to the Control
Panel.
1.2
BPA is designed to operate in SLC formed by RPA.
1.3
The number of BPAs registered in the Control Panel is up to
96 units.
1.4
BPA provides protection of control outputs
OUT1, OUT2
against
overloads, polarity reversal, voltage surges.
1.5
In the initial state, reverse polarity voltage is applied to the outputs of
the BPA, it is necessary to protect the connected load sensitive to polarity
from reverse voltage.
1.6
The outputs
OUT1, OUT2
can be operated with or without control
of the integrity of the line (depending on the configuration).
When outputs are operated with line
integrity
control
, it is necessary
to connect the
terminal elements
of the output from the delivery set to
the terminals
OUT1, OUT2
.
1.7
BPA provides:
a)
control of the power supply at the
inputs U1, GND, U2, "+", "-";
b)
switching the input voltage from 10.5 to 28.7 V from inputs U1, U2
to outputs
OUT1
and
OUT2
with switching current of each output up to
1.25 A
;
c)
control of the load line of the outputs
OUT1
and
OUT2
, separately
for open and short circuits, and transfer to the Control Panel infor-
mation about the integrity of the load line;
d)
control of the state of
4 alarm loops
of the following types: security, fire
thermal with double actuation, fire smoke with double actuation, fire com-
bined with single actuation and technological with short circuit (Open cir-
cuit) control;
e)
light indication of the BPA operation, the status of the outputs, SLC and
AL.
1.8
The power supply of the
address
part of the BPA is carried out
only
from the RPA via the SLC power line (terminals "
+
", "
-
").
1.9
The power supply of the
outputs and AL
of the part (outputs, AL)
is carried out
only
from an external power supply of 12 V or 24 V D.C.
1.10
The BPA has two independent power inputs (main and backup)
(terminals U1, GND, U2) and automatically switches from the main input to
the backup and back in case of a voltage drop or no voltage at one of the
inputs.
1.11
There is galvanic isolation between the address and signal-starting
parts. When powering the BPA and RPA from different power sources,
it is not allowed to combine their zeros, except for the case when the
BPA and RPA are powered from one set of main and backup power
sources.
1.12
The BPA provides operation with the length of the communica-
tion line of the
SLC
interface up to
1000 m.
1.13
Recommended wires for
SLC
: cable with two pairs of twisted
cores (pairs arranged in parallel), core cross section (single-wire class
1 or stranded at least class 3, from 0.35 to 2.5 sq. mm.
The recommended wire type to ensure maximum range for SLC in fire
systems is
FRLS (FRHF, FRLSLtx), 2×2×0.5.
For security systems, it is permissible to use a UTP 4
×2×0.5 cable.
2 SPECIFICATIONS
General Technical Parameters
Power supply, V ........................................................ from 10.5 to 28.7
Average current consumption* (AL1-AL4 is off.) at 12 (24) V, mA:
- without line control (OUT1, OUT2 off) .................................... 14 (15)
- with line control:
- OUT1, OUT2 off ..................................................................... 16 (17)
- OUT1 on, OUT2 off ................................................................ 19 (20)
- OUT1 off, OUT2 on ................................................................ 19 (20)
- OUT1, OUT2 on ..................................................................... 23 (24)
Inherent control current (reverse polarity)* of outputs OUT1, OUT2 in
the "Off" state (current consumption of terminal output element) at
voltage 12 (24) V, mA ................................................................... 1 (3)
Connecting each loop increases the average current consumption at
voltage 12 (24) V, mA:
- Standby mode ..................................................................... for 7 (10)
- Fire mode .......................................................................... for 12 (16)
Max. current consumption voltage 12 (24) V, mA, no more ...... 73 (94)
Max. current consumption with connected load, A, no more ........... 2.6
Max. cable cross section for connection to terminal, mm2, no more
than ................................................................................................ 2.5
Current consumption on the SLC supply line, mA, max ..................... 1
Threshold for the beginning of indication of a power failure, V:
- from an external power supply 12(24) V ...............................10.2 -0.2
- through the power line from SLC RPA ................................... 8.5 -0.1
AL Parameters (Zone1
– Zone 4):
Voltage at the inputs of the AL in the standby
mode, V ...................................................................... from 8.5 to 27.6
Effective voltage value of pulsations on AL terminals, mV, no more........ 50
Short circuit current at AL inputs, mA, no more ........................................ 30
Integration time, msec ....................................................................
300 ± 30
Resistance of wires connected to AL inputs
(excluding external element), Ohm, not more ......................................... 150
Leakage resistance between AL input wires
or each wire and "Ground", kOhm, min. .................................................... 50
Short circuit current at AL inputs, mA, not more ....................................... 30
OUT1, OUT2 parameters:
Maximum switching voltage, V ............................................................... 28.4
Maximum switched output current, A ........................................... 1.
25 ± 0.01
(in total no more (2.
50 ± 0.02) А)
Boot time, sec., no more ................................................................. 10
Overall dimensions, mm, not more ................................. 135
× 85 × 39
Weight, kg, not more .....................................................................0.35
Operating conditions
Temperature range,
°
С ................................................ from -30 to +55
Relative humidity, % ................................................ up to 93 at +40
°
С
Without moisture condensation
3 DELIVERY SET
Astra-BPA .................................................................................... 1 pc.
Resistor 3.9 kOhm ..................................................................... 4 pcs.
DIN rail mounting bracket ........................................................... 2 pcs.
Exit element terminal .................................................................. 2 pcs.
Screw ......................................................................................... 8 pcs.
Dowel ......................................................................................... 4 pcs.
__________________________________________
*
Without taking into account the power supply of the external load and de-
tectors on the loop.