ASTRA-BPA 

Addressable relay unit 

 

User Guide

 

 

 

 

 

This  operating  manual  is  intended  to  study  the  principle  of  operation, 
proper  use,  storage  and  maintenance  of  the  Astra-BPA  addressable 
relay unit. 
The  manufacturer  reserves  the  right  to  make  changes  to  the  design, 
software, circuit solutions and product packaging that do not worsen its 
technical  characteristics,  do  not  violate  mandatory  regulatory  require-
ments, without prior notice to the consumer. 
The  technical  features  of  the  product  not  specified  in  the  instruction 
manual in terms of design, software and circuit solutions are standard 
for the product, if they do not worsen the declared technical character-
istics.  

Abbreviations

:  

SLC 

 

Signaling Line Circuit; 

Addressable  devices

 

– Astra-42A smoke fire detectors, Astra-43A  heat 

fire  detectors,  Astra-45A  manual  fire  manual  call  point,  Astra-BRA  relay 
unit, Astra-MA addressable mark; 

BPA 

– Addressable relay unit; 

Tutorial 

– tutorial built into the PKM Astra Pro Configuration Module, or 

Astra-812 Pro Configuration Instructions from the keypad (available on the 
website www.teko.biz);

 

Control Panel 

 

fire alarm Control Panel "Astra-812 Pro or Astra-8945 

Pro with firmware version v5_5 and higher;  

PKM

 

Astra  Pro 

–  Astra  Pro  control/configuration  software  package 

(see on the website www.teko.biz); 

FW

 

 

Firmware; 

RPA

 

–  extender  wired  address  Astra-A  RPA  with  software  version 

v5_5 and higher; 

LP

 

– Laser Pointer Astra-942; 

AL

 

– Alarm loop (wired zone) 

 

1    FUNCTION 

 

1.1 

BPA is designed for: 

–  control  the communication line and managing  devices of the  alerting 
system and control evacuation of people in case of fire;  

–  control  and  start  of  automation  control  cabinets  (signals  "Failure", 
"Emergency",  "Automatics  disabled"  and  "  smoke  exhaust  Fan    (pump, 
lock) activated); 

–  control and service fire automatics powered by 12 V or 24 V; 

–  transmission of signals through an intermediate relay device to the in-
puts of elevator controllers, voice alerting units, etc.); 

–  control through the built-in two AL (Zone 1 – Zone 4) of addressable 
fire detectors, intrusion, technological devices (including those powered by 
AL) and transmission of notifications via SLC through RPA to the  Control 
Panel. 

1.2 

BPA is designed to operate in SLC formed by RPA.  

1.3 

The number of BPAs registered in the Control Panel is up to 

96 units.

 

1.4 

BPA  provides  protection  of  control  outputs 

OUT1,  OUT2

  against 

overloads, polarity reversal, voltage surges. 

1.5 

In the initial state, reverse polarity voltage is applied to the outputs of 

the BPA, it is necessary to protect the connected load sensitive to polarity 
from reverse voltage. 

1.6 

The outputs 

OUT1, OUT2

 can be operated with or without control 

of the integrity of the line (depending on the configuration).

 

When outputs are operated with line 

integrity

 

control

, it is necessary 

to connect the 

terminal elements

 of the output from the delivery set to 

the terminals 

OUT1, OUT2

.

 

 

1.7 

BPA provides: 

a)

 control of the power supply at the 

inputs U1, GND, U2, "+", "-"; 

b)

 switching the input voltage from 10.5 to 28.7 V from inputs U1, U2 

to outputs 

OUT1

 and 

OUT2

 with switching current of each output up to 

1.25 A

;

 

c) 

control  of the  load  line  of the  outputs 

OUT1

  and 

OUT2

,  separately 

for  open  and  short  circuits,  and  transfer  to  the  Control  Panel  infor-
mation about the integrity of the load line; 

d)

 control of the state of 

4 alarm loops

 of the following types: security, fire 

thermal with double actuation, fire smoke with double actuation, fire com-
bined with single actuation and technological with short circuit (Open cir-
cuit) control; 

e)

 light indication of the BPA operation, the status of the outputs, SLC and 

AL. 

1.8 

 The power supply of the 

address

 part of the BPA is carried out 

only

 

from the RPA via the SLC power line (terminals "

+

", "

-

"). 

1.9 

The power supply of the 

outputs and AL

 of the part (outputs, AL) 

is carried out 

only

 from an external power supply of 12 V or 24 V D.C.  

1.10 

 The  BPA  has  two  independent  power  inputs  (main  and  backup) 

(terminals U1, GND, U2) and automatically switches from the main input to 

the backup and back in case of a voltage drop or no voltage at one of the 
inputs.  

1.11 

 There  is  galvanic  isolation  between  the  address  and  signal-starting 

parts. When powering the BPA and RPA from different power sources, 
it is not allowed to combine their zeros, except for the  case  when the 
BPA  and  RPA  are  powered  from  one  set  of  main  and  backup  power 
sources. 

1.12 

  The  BPA  provides  operation  with  the  length  of  the  communica-

tion line of the 

SLC

 interface up to 

1000 m.

 

1.13 

  Recommended  wires  for 

SLC

:  cable  with  two  pairs  of  twisted 

cores (pairs arranged in parallel), core cross section (single-wire class 
1 or stranded at least class 3, from 0.35 to 2.5 sq. mm. 
The recommended wire type to ensure maximum range for SLC in fire 
systems is 

FRLS (FRHF, FRLSLtx), 2×2×0.5. 

For security systems, it is permissible to use a UTP 4

×2×0.5 cable.  

 

2  SPECIFICATIONS 

 

General Technical Parameters 

Power supply, V ........................................................ from 10.5 to 28.7 
Average current consumption* (AL1-AL4 is off.) at 12 (24) V, mA: 
- without line control (OUT1, OUT2 off) .................................... 14 (15) 
- with line control: 
- OUT1, OUT2 off ..................................................................... 16 (17) 
- OUT1 on, OUT2 off ................................................................ 19 (20) 
- OUT1 off, OUT2 on ................................................................ 19 (20) 
- OUT1, OUT2 on ..................................................................... 23 (24) 
Inherent  control  current  (reverse  polarity)*  of  outputs  OUT1,  OUT2  in 
the  "Off"  state  (current  consumption  of  terminal  output  element)  at 
voltage 12 (24) V, mA ................................................................... 1 (3) 
Connecting  each  loop  increases  the  average  current  consumption  at 
voltage 12 (24) V, mA:  
- Standby mode ..................................................................... for 7 (10) 
- Fire mode .......................................................................... for 12 (16) 
Max. current consumption voltage 12 (24) V, mA, no more ...... 73 (94) 
Max. current consumption with connected load, A, no more ........... 2.6 
Max.  cable  cross  section  for  connection  to  terminal,  mm2,  no  more 
than ................................................................................................ 2.5 
Current consumption on the SLC supply line, mA, max ..................... 1 
Threshold for the beginning of indication of a power failure, V: 
- from an external power supply 12(24) V ...............................10.2 -0.2 
- through the power line from SLC RPA ................................... 8.5 -0.1 

 

AL Parameters (Zone1 

– Zone 4): 

Voltage at the inputs of the AL in the standby 
mode, V ...................................................................... from 8.5 to 27.6 
Effective voltage value of pulsations on AL terminals, mV, no more........ 50 
Short circuit current at AL inputs, mA, no more  ........................................ 30 
Integration time, msec .................................................................... 

300 ± 30 

Resistance of wires connected to AL inputs 
(excluding external element), Ohm, not more ......................................... 150 
Leakage resistance between AL input wires 
or each wire and "Ground", kOhm, min. .................................................... 50 
Short circuit current at AL inputs, mA, not more  ....................................... 30 

 

OUT1, OUT2 parameters: 

Maximum switching voltage, V ............................................................... 28.4  
Maximum switched output current, A ...........................................  1.

25 ± 0.01 

(in total no more (2.

50 ± 0.02) А) 

Boot time, sec., no more ................................................................. 10 
Overall dimensions, mm, not more ................................. 135 

× 85 × 39   

Weight, kg, not more .....................................................................0.35 

Operating conditions 

Temperature range, 

°

С ................................................ from -30 to +55 

Relative humidity, % ................................................ up to 93 at +40 

°

С  

                                                                    

Without moisture condensation 

 

3  DELIVERY SET 

 

Astra-BPA .................................................................................... 1 pc. 
Resistor 3.9 kOhm ..................................................................... 4 pcs. 
DIN rail mounting bracket ........................................................... 2 pcs. 
Exit element terminal .................................................................. 2 pcs. 
Screw ......................................................................................... 8 pcs. 
Dowel ......................................................................................... 4 pcs. 
 
__________________________________________ 
*

 

Without taking into account the power supply of the external load and de-

tectors on the loop. 