Version 01 /
p.26
AFA1000/2 MK2 Airflow Monitor
Installation & Operating Manual
Mains Fail (Optional extra feature)
• When the input configured as Mains Fail is activated
• Red LED on
• Mains Fail is displayed
• Audible alarm sounds
• Audible can be muted via Enter pushbutton -- this silences the alarm if configured.
Fan Stop
• When the input configured as Fan Stop is activated
• Off is displayed
• Red LED on (Solid)
• Audible alarm muted
• When the input configured as Fan Stop is de-activated
• Start Up Timer is displayed
• Audible alarm and relays inhibited until Start up time has elapsed
Note - Used if the AFA1000 is a Slave unit with a common fan (Remote master On/Off signal is used)
Mute
• When the input configured as Mute and is activated
• Red LED on (Solid)
• Audible alarm muted
• Mute Icon shown on display
Note - The Mute function disables the pushbutton mute so that any audible alarm can only be
muted using the input e.g. remote key switch.