Subject to modifications and errors
Page 48 of 71
2019-06-26 edition
.025
T ULN min1
Time OFF
ms
50
50
180000
50
180000
Only active for:
Connection Modes: 2-wire, 4-wire (LN)
Overvoltage2 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.026
ULL max 2
Enable function
off
on / off
on /off
.027
ULLmax2off
U
THR
OFF
%Unom
105
100
135
100
135
.028
ULLmax2on
U
THR
ON
%Unom
110
110
110
100
135
.029
T ULL max2
Time OFF
ms
60000
50
180000
50
180000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Undervoltage2 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.030
ULL min 2
Enable function
off
on / off
on /off
.031
ULLmin2off
U
THR
OFF
%Unom
30
10
100
10
100
.032
ULLmin2on
U
THR
ON
%Unom
90
90
90
0
100
.033
T ULL min2
Time OFF
ms
50
50
180000
50
180000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Overvoltage2 Line to Neutral
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.034
ULN max 2
Enable function
off
on / off
on /off
.035
ULNmax2off
U
THR
OFF
%Unom
105
100
135
100
135
.036
ULNmax2on
U
THR
ON
%Unom
110
110
110
100
135
.037
T ULN max2
Time OFF
ms
60000
50
180000
50
180000
Only active for:
Connection Modes: 2-wire, 4-wire (LN)
Undervoltage2 Line to Neutral
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.038
ULN min 2
Enable function
off
on / off
on /off
.039
ULNmin2off
U
THR
OFF
%Unom
30
10
100
10
100
.040
ULNmin2on
U
THR
ON
%Unom
90
90
90
0
100
.041
T ULN min2
Time OFF
ms
50
50
180000
50
180000
Only active for:
Connection Modes: 2-wire, 4-wire (LN)
10 minutes average overvoltage
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.038
U avg
Enable function
on
on
on /off
.043
U avg off
U
THR
OFF
%Unom
112
110
115
100
135
U
THR
ON
% Unom
Fixed Hysteresis (1% U
NOM
)
Time OFF
Fixed to a fastest possible disconnection
Overfrequency1
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.055
f > off
f
THR
OFF
Hz
51,50
51,50
51,50
50,0
55,0
f
THR
ON
Hz
Fixed reconnection frequency of 50,05Hz
Time OFF
ms
Fixed to a fastest possible disconnection
Underfrequency 1
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.059
f < off
f
THR
OFF
Hz
47,5
47,50
47,50
45,00
50,00
.060
f < on
f
THR
ON
Hz
47,5
47,50
47,50
45,00
50,00
Time OFF
Fixed to a fastest possible disconnection
Comment:
f < on has a fixed offset of 0,01 Hz added to the displayed value
Auxiliary Contact type
Conformity Range
Possible Range