3 Assembly
3.1 Assemble radio base
When installing Wireless Smoke Detectors on the ceiling, a minimum distance of
50cm to the wall must be observed. On slanted roofs the highest point in the
ceiling should be selected. If installed on a wall, a minimum distance of 30cm and
a maximum distance of 50cm to the ceiling must be selected.
The base plate can be loosened from the radio mounting base by turning it.
Mount the base plate using the enclosed mounting materials (anchors and
screws).
When mounting, pay attention to the composition of the ceiling and the suitability
of the enclosed mounting materials. Select an installation site on the ceiling on
which secure mounting is possible.
Turn the radio mounting base on the base plate to lock it in place.
The smoke detector head must be inserted into the radio mounting base taking the
coding bar and locked into place by turning it with the help of the bayonet catch.
4 Operational Start-Up
4.1 Function test
Instruction
Do not press the button on the smoke detector head with pointed objects. Failure
to heed this instruction can damage it.
Press the button on the alarm head.
A signal tone will sound.
The LED will blink red twice.
A connection will be established with the Carephone.