Dual-Feed 600A Load Center Frame
600CB10 & 600CB12 Installation Guide
3
© Telect, Inc. All rights reserved. 7.14.17 136429-2
509.926.6000 :: www.telect.com
Outputs:
Specifications:
Max. output circuit breaker or fuse holder
Single-pole: 100A; Double-pole: 175A
Max. output load – continuous
Single-pole: 80A; Double-pole: 140A
Minimum short circuit interrupt rating
5000A
Max. total output load
550A per side
Output terminal studs (with KEPS nuts and washers) for
dual-hole compression lugs
1
/
4
-20 studs on
5
/
8
-in. centers [max. lug width of 0.625-in.
(15.8 mm) for a BATT terminal and 0.70 (17.7 mm) for a RTN
terminal]. Torque bolts (using
7
/
16
-in. or 12 wrench) to a 50-in./lb.
(5.5 N
•
m), max.
Output wire size
•
#10 AWG (min.) for a 25A single-pole interrupter to #2 AWG (min.)
for a 100A single-pole interrupter
•
#2 AWG (min.) for double-pole interrupters from 100 to 175A
•
2/0 AWG (min.) for triple-pole interrupters
•
4/0 AWG (min.) for quad-pole interrupters
Circuit breakers*
•
AIRPAX
®
-style LEL or Carling-style CA1**
Fuses and fuse holders
•
TFD fuse holders for single-pole TLS or TPS fuses
•
TPC DC-BBE-3 fuse holders for single-pole TPC fuses
•
TPW fuse holders for double-pole TPC fuses
Alarms:
Specifications:
Alarm relay contacts
2A @ 30 VDC; 0.6A @ 60 VDC
Max. alarm card power rating
@24V: 103 mA (2.47W); @48V: 128 mA (6.14W)
Alarm wire size
#24 AWG, typical (#26 to #20 AWG)
Alarm terminals
Wire wrap
Dimensions:
Specifications:
600CB10 width (all models)
600CB12 width (all models)
Height
Depth
19-in. (483 mm)
23-in. (584 mm)
3.5-in. (88 mm)
12-in. (305 mm)
Dimensions:
Specifications:
Weight, without packaging and accessories
600CB10: 18 lbs. (8.2 kg); 600CB12: 22 lbs. (10 kg)
600CB10-xL: 21 lbs. (9.5 kg); 600CB12-xL: 25 lbs. (11.3 kg)
Weight, shipping
600CB12: 25 lbs. (11 kg); 600CB12: 30 lbs. (14 kg)
600CB12-xL: 28 lbs. (12.7 kg); 600CB12-xL: 33 lbs. (15 kg)
Environment:
Specifications:
Operating temperature
-10
°
C (14
°
F) to 55
°
C (131
°
F)
Humidity
90%, non-condensing
Compliance:
Specifications:
UL Recognized, NEBS Level 3
*
Telect suggests you avoid using different types of circuit breakers or fuses in the same load center. Alarm contacts may
vary among interrupter manufacturers and may incapacitate the alarm system.
** Circuit breakers for this load center are designed and manufactured by Airpax Corporation and Carling Industries to
meet Telect’s specifications. Order circuit breakers only from Telect.