Page 62
Telect, Inc. • USA +1.509.926.6000 • 52.33.3836.37.52
www.telect.com • © 2011 Telect, Inc., All Rights Reserved, 139249-1 A0
16. Make sure that the DC power system has sufficient capacity. See “A. Rectifier Load Limits” on
17. Turn on the enclosure light switch (Figure 65).
18. Turn on the GFI breaker switch (Figure 65).
19. Check that the GFI has power (Figure 67).
20. Turn on the Heater breaker switch (Figure 65). The heater will only come
on if the temperature is less than 50
o
F.
21. Disable the Door Open alarm by pulling out the plunger (Figures 65 & 68).
22. Check the Controller LED screen for any alarms. All alarms should be cleared after every-
thing is turned on. If any alarms remain on, see the “Troubleshooting” chapter in the
nrg-
SMART™ 24RU Enclosure IOE-24S-XXXX User Manual,
Telect part number 138655.
23. Push the Door Open alarm plunger back in to its normal state.
24. Charge the batteries according to the battery manufacturer’s recommendations.
This procedure is complete.
Figure 67 - GFI
Plunger in normal state
Plunger alarm disabled
Figure 68 - Door Open Alarm Switch