background image

Dual 40/50/100A Configurable Breaker Panel

Power

 :: T009-5XXXXXXXXXXX

© Telect, Inc.,  All Rights Reserved, 118267-3 A0

1.509.926.6000  ::  telect.com

2

Installation Guide 

Mechanical 

Specifications 

Dimensions (nominal), without brackets* 

Width: 17.25" (43.82 cm)
Height: 1.75" (4.44 cm)
Depth: 8.00" (20.32 cm)

Weight without breakers 

9 lbs (4.08 kg)

Weight, shipping

10.5 lbs (4.76 kg)

Mounting for standard racks

EIA: 19" (48.2 cm)
WECO: 23" (58.4 cm)
ETSI: 21" (53.3 cm) 

 

[Kit sold separately. See “Accessories” (Page 7).]

Ground terminals 

Quantity: 

Stud:       

Lugs:      

Cable:     

Torque: 

2

M5 with hex nut. [Use 8mm 

 

(5/16 in.) socket.]

Single or dual-hole compression lug [5/8 in. 
(1.59 cm) center to center]
Up to #10 AWG for single-hole lug 

Up to #6 AWG for dual-hole lug. 

 

(Conductor size depends on input 

 

interruption device.)

20 in.-lb (~2.25 N•m), max.

Input terminals — Compressions

Quantity: 

Stud: 

Lugs:

Cable: 

Torque: 

4 — 2 BATT, 2 RTN

M5 with KEPS nut. [Use 8 mm 

 

(5/16 in.) socket.]

Dual-hole compression lug

[5/8 in. (1.59 cm) center to center]

Up to #1 AWG, depending on input 

 

interruption device

20 in.-lb (~2.25 N•m), max.

Input terminals — Phoenix-style screw-tight

Slotted screwhead for wire clamping up to

#6 AWG, depending on input interruption

device. Torque screws to 14 in.-lb (~1.5 N•m).

Output terminals — Wire binding

Quantity: 

Screw: 

Cable: 

Clearance: 

Torque: 

28 — 14 BATT, 14 RTN

#6 Phillips** pan head

Up to #10 AWG

0.31 in. (.79 cm) between terminal barriers

9 in.-lb (1.02 N•m), max.

Alarm terminals — Wire binding 

Quantity: 

Screw: 

Cable: 

Torque

6

#4 Phillips** pan head

#30 to #16 AWG

4 in.-lb (0.45 N•m), max.

Specifications

* See Page 11 for 

 

exact dimensions 

** Screws with 

 

cross-recessed heads

Summary of Contents for T009-5 Series

Page 1: ...ompression inputs only White or black panels can be configured with any combination of 1A to 20A Carling M Series breakers oriented with the on symbol at either the bottom or top 50A thermal input bre...

Page 2: ...r dual hole lug Conductor size depends on input interruption device 20 in lb 2 25 N m max Input terminals Compressions Quantity Stud Lugs Cable Torque 4 2 BATT 2 RTN M5 with KEPS nut Use 8 mm 5 16 in...

Page 3: ...omer Service Department at 1 800 551 4567 domestic only or 1 509 926 6000 for further recourse NOTE Panel brackets provide either flush or extended EIA or WECO mounting in a 19 or 23 rack Panel is con...

Page 4: ...insi que pour l quipement ALERT ALERT Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region such as Underwriter s Laboratories UL TUV et...

Page 5: ...tighten to 14 in lb 1 5 N m Compression Lug Inputs Screw Tight Vertical Horizontal Inputs Alarm Indicators 9 Make sure power is off open breaker dummy fuse or open fuse holder at power distribution u...

Page 6: ...l breaker out puts on each side must not exceed 40A for a panel with an optional thermal input breaker 50A for a panel having screw tight inputs connectors but without an optional thermal input breake...

Page 7: ...aced Then turn off input power to that side of panel 4 Place breaker to be replaced in the off position 5 Using a very small flat tipped screwdriver carefully pry out on bottom of breaker while applyi...

Page 8: ...nting Brackets Black 090 0041 0030 White 090 0041 0031 Front Cover Clear 090 0001 0001 Designation Label 1 7 A B 115353 ALERT The LINE side connection of the breaker has live VDC Do not allow contact...

Page 9: ...is closed and C to NO is open Input Power Failure POWER ON A or POWER ON B LED s will go off POWER FAIL relay de energizes so that C to NC opens and C to NO closes Input Breaker Opens input breakers...

Page 10: ...e Inputs Wire Binding A Side Inputs Compression Inputs With 50A Input Breakers Screw Tight Horizontal Inputs Without 50A Input Breakers Compression Inputs Without 50A Input Breakers 100A max side Scre...

Page 11: ...akers Installed with On at Top 3 White Enclosure Breakers installed with On at Top Panel Color Breaker Orientation 0 Screw Tight Horizontal Inputs with 50A Thermal Input Breakers Inputs Type of Connec...

Page 12: ...r its patent rights or the patent rights of others This document and the products described herein are subject to change without notice INPUT BREAKER B BATT 24V 48V 100A MAX 24V RTN BATT RTN GND CHS C...