OLCT 60
FIXED POINTGAS MONITOR
USER MANUAL
NPO60GB
Revision F.2
11
Figure 14: GD10P detector MUST be laid horizontally, indicator pointing upwards
Figure 15: OLCT IR detector must be laid horizontally, indicator pointing upwards
2.5
Electrical Specifications
Type of sensor
Input Voltage
(Vdc)
Maximum
current (mA)
Power
consumption
(W)
Catalytic
16 to 32
140
2.5
Infrared (sensor)
16 to 32
120
2.0
Infrared (GD10P)
18 to 32
300
7.2
Electrochemical
16 to 32
80
1.3
Semiconductor
16 to 32
140
2.5
3 meters minimum
30 meters maximum