20
NPO60GB
Revision F.2
4. Apply the gas (flow regulator set to 0.5-1.0 liter per minute (LPM). For GD10P versions refer to
GD10P manual.
5. Once the measure is stabilized (approx. 2 minutes), read the value on the display (rep. A).
6. If the expected value does not comply, proceed with the calibration (paragraph
Zeroing and
sensitivity adjustment, on page 26).
7. Continue with
Checking gas sensitivity on the next page.
3.7
Checking gas sensitivity
For safety reasons, this procedure must be carried out after the control of the zero (page 18).
Proceed as follows:
Figure 27: Checking gas sensitivity
1. Once the detector is zeroed, connect the calibration cup to the calibration gas cylinder (Pos.
E) by using a tubing in PTFE (Pos. C) to prevent the adsorption of reactive gases (i.e.: HCl,
SO2, Cl2, etc.) at the surface of the tube.
2. Open the valve on the gas cylinder (flow rate 0.5 to 1 LPM. In the case of GD10P versions
refer to GD10P manual.
3. Once the measurement is stabilized (approx. 2 minutes), read the value on the display (rep.
A).
4. If the expected value does not comply, proceed with the calibration (paragraph Zeroing and
sensitivity adjustment, on page 26).
5. Close the valve (rep. D) of the gas cylinder and remove the calibration cup (rep. B). Wait for
the measurement to return to zero and reset the alarms on the controller. The control of zero
and gas sensitivity is now completed.
Summary of Contents for OLCT 60
Page 1: ...NPO60GB Revision F 2 OLCT 60 FIXED POINTGAS MONITOR USER MANUAL ...
Page 44: ...OLCT 60 FIXED POINTGAS MONITOR USER MANUAL 38 NPO60GB Revision F 2 ...
Page 50: ...OLCT 60 FIXED POINTGAS MONITOR USER MANUAL 44 NPO60GB Revision F 2 ...
Page 52: ...OLCT 60 FIXED POINTGAS MONITOR USER MANUAL 46 NPO60GB Revision F 2 ...
Page 66: ...OLCT 60 FIXED POINTGAS MONITOR USER MANUAL 60 NPO60GB Revision F 2 ...
Page 67: ...OLCT 60 FIXED POINTGAS MONITOR USER MANUAL NPO60GB Revision F 2 61 ...