OLCT 60
FIXED POINTGAS MONITOR
USER MANUAL
28
NPO60GB
Revision F.2
5.4.3
Adjustment of gas sensitivity
Accessing the sensitivity adjustment menu
Step
Action
Illustration
3a
«GE» (
Span Gas) is displayed to indicate that the system has
switched over to the sensitivity adjustment phase.
Setting the Span Gas concentration
Step
Action
Illustration
4a
Place the magnet over
.
4b. The displayed value corresponds to the span gas value by
default (50 in the example).
The hundreds digit flashes.
4c. Adjusting the hundreds
Adjust the value of the hundreds by placing the magnet over
. Each time you place the magnet over, you increase the
digit value.
4d. Confirm the value by placing the magnet over
.
4e. Adjusting the tens
The tens digit flashes. Repeat the same procedure as for the
hundreds.
4f.
Adjusting the units
The unit digit flashes. Repeat the same procedure as for the
hundreds.
4g
Validate the digit of the units by placing the magnet over
.
4h. End of the procedure.
Injecting calibration gas
Step
Action
Illustration
5a. The display indicates «S» (Sensitivity).
5b. Place the calibration cup on the sensor and inject the span gas
at flow rate between 0.5 and 1 LPM (for GD10P versions refer
Summary of Contents for OLCT 60
Page 1: ...NPO60GB Revision F 2 OLCT 60 FIXED POINTGAS MONITOR USER MANUAL ...
Page 44: ...OLCT 60 FIXED POINTGAS MONITOR USER MANUAL 38 NPO60GB Revision F 2 ...
Page 50: ...OLCT 60 FIXED POINTGAS MONITOR USER MANUAL 44 NPO60GB Revision F 2 ...
Page 52: ...OLCT 60 FIXED POINTGAS MONITOR USER MANUAL 46 NPO60GB Revision F 2 ...
Page 66: ...OLCT 60 FIXED POINTGAS MONITOR USER MANUAL 60 NPO60GB Revision F 2 ...
Page 67: ...OLCT 60 FIXED POINTGAS MONITOR USER MANUAL NPO60GB Revision F 2 61 ...