In case only one alarm triggered the alarm verification clock, during and up to 120
seconds, no additional alarm is received, the clock will be reset and the control panel will
be back in normal mode.
3.2.2 Alarm Operations
During an alarm in one of the addresses, the control panel performs the following
operations
Indicating the address in alarm on the LCD display
Turning on the Fire LEDs in the LCD display and clarification area and the private
alarm zone in the zoning alarm
Displaying the alarm in the remote panel RM-7000 if connected
Logging an event in alarm history
Activating the NAC outputs in the panel
Activating dialer output
Activating internal buzzer
Activating relays that were configured as alarm relays
Activate output addresses as per matrix configuration
3.2.3 Acknowledge / Buzzer Off Operation
Silences the internal buzzer
UL 864
UL Models
For UL models, pressing the
Acknowledge
key will stop the flashing of the
LEDs and turn them solid on.
3.2.4 Acknowledge Operation
3.2.5 Silence Operation
Pressing the
Silence
key performs the following actions
Stops the action of the horn output
Stops the action of the internal buzzer
Stops the alarm relay if it was programmed as silenceable
Stops outputs that were programmed as silenceable
3.2.6 Action during a Second Alarm (Two Devices in Alarm at the
Same Time)
Screen 3 Two concurrent alarms
When receiving a second alarm, (i.e., two devices are in alarm at the same time), the
control panel perform the following operations
Reactivation of all silenced output