The Control panel supports fire extinguishing Hold (EN 12094) / Abort (UL 864) buttons.
A device defined as a fire extinguishing Hold (EN 12094) / Abort (UL 864) button delays
fire extinguishing activation as long as the button is pressed.
Releasing the button will resume the countdown that had been suspended while the
button was pressed, if the countdown had not ended. If the countdown had ended, fire
extinguishing will activate within 5 seconds after the button was released.
Pressing the Extinguishing activation call point overrides this function.
See chapter 8 on page 41 for a detailed explanation about device programming.
5.4
Extinguishing Disconnect
UL 864
UL Requirement
UL 864 requires that extinguishing disconnect shall be a physical switch and
not accomplished by software.
Extinguishing disconnect shall be shown as a supervisory event.
An extinguishing disconnect switch shall be installed near the extinguishing
device.
Activating the cut off extinguishing switch (a key) will cut off the fire extinguishing output
circuit. The fire extinguishing output circuit will be deactivated until the switch is returned
to normal mode
– this is intended for use during service and/or maintenance work.
The extinguishing disconnect is displayed on the control panel as a supervisory event.
The extinguishing disconnect switch will be installed near the fire extinguishing device.
Figure 14 Extinguishing disconnect switch
See chapter 8 on page 41 for a detailed explanation about device programming.
5.5
Extinguishing Notification and Action to Perform after Release
After extinguishing activation, the display will indicate that an extinguishing device was
activated.
Pressing the
Reset
key will not cancel this indication in order to ensure cylinder
replacement or refill.