ADR-7000 / SAVER-7000 / GUARD-7
© 2017
– Telefire Fire & Gas Detectors Ltd
Revision 0.98 October 2017
– Page 39 of 87 –
UL
UL 864 paragraph 59.1 Compliance
The ADR-7000 product family is UL 864 complaint, and does not allow setting
that contradict the standard's requirements.
The following products mentioned in this manual were not tested or listed by
UL and should not be installed where UL listing is required:
TFH-280A and TFH-220A (Heat Detectors)
ADR-812A and ADR-818A (Input modules)
TPS-34A (auxiliary power supply
– use a UL listed 24Vdc power supply)
TIP-224A (Sounder)
ADR-833A (Extinguishing controller)
TPH-482A and TPH 442A (photo / heat multi-sensor detectors)
7.2
Entering Configuration State
Press Menu and select
1 System Program
. Enter the password and press
Enter
.
7.3
Configuration Process
Programming the system is in five steps:
Enter programming state
Program control panel general setting
Program device-specific parameters for input devices
Program output devices / NACs operating mode and activation conditions
Save system configuration
i
Note
After about 30 minutes without keyboard activity during programming mode
the control panel's buzzer is activated to remind you not to leave the system
in programming mode.
7.4
Saving the Configuration and Exit Out of System Configuration
When exiting programming mode the control panel will display a menu with 3 choices:
1
– save and exit
2
– discard changes and exit
#
– cancel exit and go back to programming
Select the desired option by pressing the appropriate key.