8.5
Utilities
8.5.1 Lamp Test
Lamp test turns on all LEDs in the keyboard / display and activates the internal buzzers
for a few seconds.
8.5.2 Clear Activated Extinguisher
Screen 31 Clearing Extinguishing activated indication
Activation of an extinguishing output will result in a notification in the control panel that
extinguishing was activated. Pressing the
Reset
key will not cancel this indication in
order to ensure extinguishing agent replacement or refill.
To return the control panel to normal operation refill or replace the extinguishing device,
select the clear activated Extinguisher menu by pressing
Menu
, selecting
5 Utilities
,
and selecting
2 Clear Activated Extinguisher
. Press Enter and ensure that the control
panel is back to Quiescence state.
This operation shall be performed only by authorized personnel.
8.5.3 Revisions
This option shall display hardware and software revisions of the following modules:
1. CPU Card (ADR-7007)
2. SLC cards (ADR-7002)
3. Main Board (ADR-7021)
4. Display Card (ADR-7003)
5. LON Card (LON-7000)
6. TCP/IP Net Card (NET-7000)
7. Remote Displays (RM-7000)
8. Site Specific Data
– Device Configuration
9. Site Specific Data
– System Configuration
8.5.4 Keyboard Locking
The
Keyboard Locking
function prevents unauthorized people from activating functions
by pressing accidentally the operator keys such as silencing an alarm or reset.
When the keyboard is locked, no action can be taken in the system, except
acknowledge, browsing the memory and displaying alarm and trouble events.
The ADR-7000 default configuration is locked keyboard.
To change the keyboard locking mode, go to the Utilities menu and select
Keyboard
Locking
. You will need to enter the programmer password to access this submenu.
The Up/Down arrow keys change the locking mode.
Changing to
Unlocked
mode enables the operator/programmer access to silence and
reset functions without entering a password.