Night
– Continuous operation in night mode (without automatic change).
Time-Related
– Automatic shifting from Day to Night mode and vice versa,
according to time settings.
Select one of the modes by using the Up / Down keys. At Time-Related mode, each
weekday can be programmed by selecting a day and then setting the nighttime between
night start and night end.
Different time settings can be set for each day of the week. Use the arrow keys to toggle
between fields.
Detector sensitivity will change according to the day and night sensitivity settings of each
detector.
The Day / Night modes also affect dialer operation. An alarm that occurs during night
mode will activate the dialer immediately. During day mode operation will be delayed if
programmed thus.
Screen 34 Setting daily night and day times
8.5.7 Holidays Setting
Here you can define public holiday (referred to in some countries as "national holidays"
or "bank holidays") dates. The cont4rol panel shall work as nighttime mode all day.
Screen 35 Setting holiday dates
8.5.8 Volt / Current Measurements
Allow measuring voltages and currents in the control panel:
1. Power and battery: power supply voltage; battery voltage; battery charging current;
charging cycle.
2. NAC Outputs: NAC 1 and NAC 2 voltages and current
3. 24Vdc Outputs
– Main board: 24V_A and 24V_B, and Dialer output voltages and
current
4. 24Vdc Outputs
– Loop expansion board: 24V_C and 24V_D voltages and current
5. Loop cards: input voltage and current draw
6. Alarm Dialer: voltage and current
7. Fault Dialer: voltage and current
8. Ground Fault graph