UL 864 Compatibility
Telefire's ADR-7000 product line complies with the requirements of several standards,
including UL 864, IS 1220, EN 54, EN 12094, and GOST, and may comply with options
or requirements of one of the standards and are not compliant with another standard.
Where the control panel allows setting of a parameter that are outside the range of one
of the standards, we included an appropriate warning in the relevant area of the manual.
Parameter
Allowed?
Possible Range
Range per UL 864
Alarm verification
by delayed
confirmation
Yes
0-50 seconds
0-60 seconds
Do not combine time-based
alarm verification and cross
zone alarm verification
Alarm verification
by cross-zone
Yes
Cross zone or no
verification
Cross zone or no verification
Do not combine time-based
alarm verification and cross
zone alarm verification
Delay of releasing
Yes
0-50 seconds
0-60 seconds
Delay of first fault
in an addressable
device
Yes
0-240 seconds
0-180 seconds
Delay of buzzer
notification of loss
of AC power
Yes
0-240 minutes
0-3 minutes (0-180 seconds)
Keyboard locking
Yes
Continuously; after
10 minutes; after
30 minutes; after
an hour
0-30 minutes
UL
UL 864 paragraph 59.1 Compliance
The following products mentioned in this manual were not tested or listed by
UL and should not be installed where UL listing is required:
TFH-280A and TFH-220A (Heat Detectors)
ADR-812A and ADR-818A (Input modules)
ADR-828A (LED Driver)
TPS-34A (auxiliary power supply)
TIP-224A (Sounder)
ADR-833A (Extinguishing controller)
TPH-482A and TPH 442A (photo / heat multi-sensor detectors)
Use a UL listed equivalent product where required.