ADR-7000 / SAVER-7000 / GUARD-7
© 2017
– Telefire Fire & Gas Detectors Ltd
Revision 0.98 October 2017
– Page 57 of 87 –
Screen 53 System configuration
– NAC output
8.9.9 Relays
This menu allows you to configure the operation of the main board's 3 relays. You can
select between Alarm, Supervisory, Fault, and Pre-Alarm.
Screen 54 System configuration
– relays
8.9.10 Alarm Dialer 1
This menu allows you to configure the alarm dialer's activation conditions: will it be
activated by any panel on the network that is defined as Partner or only from this panel;
and the activation delay during day time hours (0
– 9 minutes, in 1 minute increments).
Screen 55 System configuration
– alarm dialer 1
8.9.11 Dialer 2 (Tr)
This menu allows you to configure the FWRE dialer's activation conditions: will it work as
in FWRE model (Fault Warning Router Equipment
– in this mode it is always on and
switches off at any fault), or in FB mode (activated by either 2 detectors or any call
point); will it be activated by any panel on the network that is defined as Partner or only
from this panel; and the activation delay during day time hours (0
– 9 minutes, in 1
minute increments).
Screen 56 System configuration
– alarm dialer 2