Screen 60 System configuration
– loop expansion card
8.9.16 Ground Fault
This menu allows you to change the control panel's sensitivity to ground faults, or
disable it completely.
Screen 61 System configuration
– ground fault
8.9.17 Inhibit Alarm Silence
This menu allows disabling the option to silence alarms for a certain time after alarm
initiation. Leave this option at the default unless required by local standard, regulation,
or authority having jurisdiction.
CP 10
CP 10 Requirement
CP 10 requires that under certain conditions alarms should not be silenced
for 3 minutes after first alarm. Change this value to 180 seconds if your local
standard requires it.
Screen 62 System configuration
– inhibit alarm silence
8.9.18 First Fault Delay
This menu allows delaying first fault indication of addressable devices for a short time to
avoid temporary faults. Applies only to first fault
– repeat faults will be displayed
immediately.
Range: 0
– 240 seconds. Default: 0 seconds.