Screen 63 System configuration
– first fault delay
UL
UL Requirement
UL 864 compliance requires this value to be less than 180 seconds.
IS 1220
IS 1220 Requirement
IS 1220 compliance requires this value to be less than 180 seconds.
8.9.19 AC Fault Buzzer Delay
This menu allows to delay activating the fault buzzer in case of loss of AC mains supply.
The fault is indicated visually immediately, regardless of this delay.
Range: 0
– 240 minutes. Default: 0 minutes.
Screen 64 System configuration
– AC fault buzzer delay
UL
UL Requirement
UL 864 compliance requires this value to be less than 180 seconds.
IS 1220
IS 1220 Requirement
IS 1220 compliance requires this value to be less than 180 seconds.
8.9.20 Communication with ADR-3000
When set to
Yes
(default) the control panel shall warn that passwords were not changed
from the factory set defaults. Warnings start a month after first installation and will
repeat any time a password is required.