Error Messages
Possible Cause
Repair Action
The area matrix includes
a region that was
removed from the
programming
This message will be
received when a region's
definitions are changed in an
input device or when an input
device is cancelled in a way
that causes a region that was
previously defined for
activation of an output device
is no longer active.
Reactivate the disabled
detectors or remove the
missing from output device's
list of areas
The device matrix
includes a device which
has been removed from
programming
Restore the device to the
programming matrix or
change the matrix settings
The number of sirens
cannot be greater than
the number of
the selected alarm areas
An alert that the number of
areas enabled to activate an
output device is larger than
the total number of areas in
the matrix
Reduce the number of areas
under alarm necessary to
activate the output device or
add areas so that their
number will be higher than
the necessary minimum for
activation
The number of sirens
cannot be greater than
the number of devices in
the selected areas
An alert that the selected
number of alerts required to
activate an output device is
greater than the total number
of input devices in the
selected under the matrix
Reduce the number of input
devices required to activate
the output device or add
devices in the area so that
the number is larger than the
necessary minimum for
activation
The number of alarms
cannot be greater than
the number of alarm
devices in the area: #
An alert that the selected
number of alarms necessary
in one area to activate an
output device is larger than
the total number of input
devices in one of the areas
selected to activate the
device matrix
Reduce the number of input
devices required to activate
an output device or
add devices the area where
the number of devices is too
low under the activation
matrix
The number of alarms
cannot be greater than
the number of selected
alarm devices
Activate the device or
remove the device from the
output device operational
matrix
The wrong device type
The type of device in the field
does not match the
programmed definition
A locked control panel with
unlocked detectors or an
unlocked control panel with
locked detectors
Correct the device definitions
(programming) or adjust the
type of device to match the
instructions
Replace the control panel or