ADR-7000 / SAVER-7000 / GUARD-7
© 2017
– Telefire Fire & Gas Detectors Ltd
Revision 0.98 October 2017
– Page 82 of 87 –
At least one and no more than two line cards (ADR-3002 and ADR-3002C) of any
combination can be installed in the ADR-7000.
Only one module (NET-7000 or GIM-232) can be installed in the lower expansion slot.
Quiescence
Alarm
Device
QTY
Current
Total
Current
Total
S
L
C con
n
e
cted
mo
d
u
les a
n
d
devices
ADR-712
{ } X
50 mA =
mA =
ADR-718
{ } X
50 mA =
mA =
ADR-723
{ } X
0.9 mA =
mA =
ADR-812A
{ } X
11.5 mA =
80.0 mA =
ADR-818A
{ } X
40.0 mA =
100.0 mA =
ADR-823A
{ } X
4.0 mA =
32.0 mA =
ADR-828A
{ } X
10.0 mA =
125.0 mA =
ADR-833A
{ } X
20.0 mA =
120.0 mA =
TIP-224A
{ } X
0.1 mA =
45.0 mA =
RM-4005
{ } X
40.0 mA =
70.0 mA =
TLA-22
{ } X
2.0 mA =
0.0 mA =
TLA-23
{ } X
2.0 mA =
0.0 mA =
TLA-33
{ } X
3.0 mA =
0.0 mA =
TLA-42
{ } X
2.0 mA =
0.0 mA =
TLA-44/1 or
TLA-44
{ } X
5.0 mA =
0.0 mA =
TLA-110
{ } X
1.5 mA =
0.0 mA =
TLA-120
{ } X
1.5 mA =
0.0 mA =
TLA-130
{ } X
1.5 mA =
0.0 mA =
TLA-140
{ } X
1.5 mA =
0.0 mA =
TLA-150
{ } X
1.5 mA =
0.0 mA =
TLA-160
{ } X
1.5 mA =
0.0 mA =
TLA-165
{ } X
1.5 mA =
0.0 mA =
TLA-170
{ } X
1.5 mA =
0.0 mA =
TLA-180
{ } X
1.5 mA =
0.0 mA =
TLA-190
{ } X
1.5 mA =
0.0 mA =
TFP-3000
{ } X
34.0 mA =
80.0 mA =
TFP-1CP
{ } X
0.0 mA =
2.0 mA =
TFP-806
{ } X
0.0 mA =
2.0 mA =
TFP-828
{ } X
10.0 mA =
125.0 mA =
Other NAC
{ } X
mA =
mA =
Other NAC
{ } X
mA =
mA =
Other NAC
{ } X
mA =
mA =
Total 24Vdc
current
consumption
(c)
(d)
Table 4
Power Requirement
– 24Vdc
First fill in the quantities of devices attached to the system in Table 3 and calculate total
current load of the internal configuration and load on the SLC loop.
Secondly calculate the power draw from the system’s 24V output (Table 4).