ADR-7000 / SAVER-7000 / GUARD-7
© 2017
– Telefire Fire & Gas Detectors Ltd
Revision 0.98 October 2017
– Page 3 of 87 –
2
ADR-7000 Control Panels
The ADR-7000 control panel provides user-friendly operation. The keyboard and the
display that are mounted on the front panel contain an illuminated 260-by 64 pixel
graphical LCD, LED indicators for major events, and functional keys. Access to all
operations is secured by multi-level passwords.
The interior section of the cabinet is secured by a key-lock. It contains a power supply,
the main board, line card(s), battery compartment space, and optional communication
modules.
The ADR-
7000’s main board can contain one to four ADR-7002 line cards, enabling
control of as many as 508 addressable initiating devices, notification appliances and I/O
modules. Each line card can be configured as a Class B or Class A loop.
An optional expansion modules allows the installation of up to four additional
ADR-7002 line cards (up to 1,016 addresses per control panel).
The system can be expanded beyond the base control panel by networking. An optional
LON-7000 network communication module allows the connection of as many as 32
control panels to set up a peer-to-peer network. With appropriate programming each
control panel on the network is able to respond to alarm and trouble events that occurred
in other control panels.
The control panel has an integral real time clock and calendar that enables day and
night sensitivity setting for each addressable detector according to weekly operation
schedule and working hours. Daytime and nighttime hours can be programmed
independently for each day of the week, as well as national holidays.
Events such as alarm, trouble, silencing, reset, programming, etc., are stored in the
ADR-
7000’s memory in the order in which they occur, creating event-list history. An
event record contains date, time, device type, and additional details. Event records can
be displayed on screen and printed as a report.
All op
erations and configuration can be performed either from the system’s front panel or
from a PC. Telefire’s user-friendly proprietary programming and control software
(running on Windows™ operating system) allows operators/installers to easily configure
any system parameter using its advanced graphical interface.
ADR-7000 control panel for a variety of communication interfaces that allow control and
monitoring;
RS 232 connection to a computer, NET-7000 TCP/IP module for control and
monitoring via a local (LAN) or global (WAN) area network
RS-485 for Class B or Class A connection to remote annunciators
USB connector for connecting to a computer