background image

70

 -

TBD

 

 

 

                                 

©

2007-2020

 

A

LL RIGHTS RESERVED TO 

T

ELE

F

IRE 

F

IRE AND 

G

AS 

D

ETECTORS 

L

TD

.

                                            

R

EVISION 

1.11

 

F

EBRUARY 

2020

 

     

Page 

12 of 19 

 

Here you can change the beam behavior. Press 

Enter

 to enter 

the mode change menu and sub-menus. 

 

 

 

Press the left and right arrow keys to increase/decrease the 
beam sensitivity. The default is 35% (meaning the received 
signal has to decrease by 35% to activate the alarm relay. This 
sensitivity can range between 25-50%). Press 

Enter

 to return 

to 

Mode Change

 or the down arrow to enter 

Time to Fire

.  

 

Here you can set how much time the beam has to be in Time 
to Fire state before it activates the alarm relay. As default, this 
time is set to 10 seconds. You should increase this time if 
there are interferences like birds, lifting platforms etc. This time 
can be set between 2-30 seconds, by pressing the left and 
right arrows (press 

Enter

 to return to 

Mode Change

 or the 

down arrow to 

Time to Fault

.  

 

Here you can set the fault time between 2-60 seconds by 
pressing the right and left arrows (the default is 10 seconds). 
In order for the beam to enter fault mode, the beam has to be 
completely blocked within 1 second (press 

Enter

 to return to 

Mode Change

 or the down arrow for 

Auto Reset

.  

 

 

The detector's default is 

Auto Reset

, when the received signal 

exceeds the alarm threshold. The detector can be set to 
latching alarm, by the right and left arrows. Press 

Enter

 to 

return to 

Mode Change

 or to down arrow to enter 

Auto Reset

.  

 

 

Align On/Off

 allows to cancel the auto alignment function for 

compensation. For example, in an environment where there is 
a lot of smoke from welding, Auto Alignment will be on when 
the received signal is less than 90%, the value at which the 
beam automatically checks for structure displacements. The 
beam will try to align through the smoke, which can be difficult 
if the beam does not detect the reflector edges. Use the right 
and left arrows to switch it on and off. When this function is 
disabled, check that the detector is installed on a rigid surface, 
free from movements. Auto Alignment will still be enabled in 
commissioning state (press 

Enter 

to return to 

Mode Change

 

or the down arrow to go to 

Align Time

.  

 

The default is 4 hours. It can be changed, using the left and 
right arrows, between 0 and 12 hours.  

 

Summary of Contents for FireBeam Xtra

Page 1: ...Detector for Automatic Alignment Displacement Compensation Technical instructions TELEFIRE FIRE AND GAS DETECTORS LTD P O Box 7036 Petach Tikwa 49250 Tel 03 970 0400 Fax 03 921 1816 Email info telefir...

Page 2: ...i Please Note Do not install operate or conduct maintenance operations in the device before reading this manual thoroughly 2007 2020 ALL RIGHTS RESERVED TO TELEFIRE FIRE AND GAS DETECTORS LTD...

Page 3: ...ND GAS DETECTORS LTD REVISION 1 11 FEBRUARY 2020 Page 1 of 19 1 Operation range and location 1 1 Operation range FIREBEAM Xtra detectors can be installed at three distance ranges 7 70 m detector prims...

Page 4: ...ctor on a solid and stable structure Install the detector at a level of 2 7 m minimum from the floor to prevent the passage of people and equipment through the beam Also take into account the traffic...

Page 5: ...cting the connector and tightening it to the base with the Allen key supplied with the detector 2 2 Installation of the control unit Install the control unit at a suitable level taking into account ac...

Page 6: ...70 TBD 2007 2020 ALL RIGHTS RESERVED TO TELEFIRE FIRE AND GAS DETECTORS LTD REVISION 1 11 FEBRUARY 2020 Page 4 of 19 2 3 Wiring...

Page 7: ...to change language use the right and left buttons to select the desired language When you finish selecting the desired language press Enter 5 Press Enter The Normal Fast screen will be displayed In m...

Page 8: ...n and Enter to enter a manual adjustment mode Caution If a free radius of 50 cm is impossible and the detector beam is obstructed by objects the IR intensity will stop increasing and the beam alignmen...

Page 9: ...gnment 10 When the value of AQ is higher than 100 manually press Enter to exit manual mode and then press Enter to enter Auto Alignment mode Auto alignment is an automatic process that first reduces t...

Page 10: ...R Cover the prims entirely and quickly If the beam is well aligned an error message will be displayed after 10 seconds The yellow fault lamp on the detector head and on the control unit will be flashi...

Page 11: ...y reading the resistance on the grey and black terminals If connected 110 Ohm has to be shown and if disconnected the resistance will be 220 Ohm This screen is displayed when the beam conducts alignme...

Page 12: ...Enter to enter the system menu Then press Down to browse the main menu options Press Enter to change the language Press Enter to align the detector Press Enter to set the detector settings sensitivity...

Page 13: ...100 the message Pre Align Complete will be displayed Otherwise a too high output power was obtained because of reflection of light from an adjacent object Use the left right up and down arrow keys to...

Page 14: ...conds In order for the beam to enter fault mode the beam has to be completely blocked within 1 second press Enter to return to Mode Change or the down arrow for Auto Reset The detector s default is Au...

Page 15: ...such that if the beam is set to alarm mode at 65 threshold of 35 the beam intensity has to reach 15 80 before it returns to normal state This operation prevents fluctuations in the reflected signal c...

Page 16: ...The relay will not be released before the Time to Fire expires This value can be between 2 30 seconds Press the left back arrows to end the test Fire Test will be displayed Press the left back arrows...

Page 17: ...70 TBD 2007 2020 ALL RIGHTS RESERVED TO TELEFIRE FIRE AND GAS DETECTORS LTD REVISION 1 11 FEBRUARY 2020 Page 15 of 19...

Page 18: ...ext to the ceiling Therefore the detector has to be installed on the building wall at least 50 cm and no more than 1 m below the ceiling to meet the requirements of NFPA 72 UL 268 and Israeli Standard...

Page 19: ...ETECTORS LTD REVISION 1 11 FEBRUARY 2020 Page 17 of 19 4 2 Connection to TSA 1000 panel Drawing 2 Connection of Fire Beam detector to TSA 1000 panel Note When connecting a beam detector to TSA 1000 pa...

Page 20: ...S LTD REVISION 1 11 FEBRUARY 2020 Page 18 of 19 4 3 Connection to TSA 200 TSA 240 panel Drawing 3 Connection of Fire Beam detector to TSA 200 TSA 240 panel Note When connecting a beam detector to TSA...

Page 21: ...t Dimensions W x H x D 120 x 185 x 62 mm Weight 0 55 kg Mid range prism 40KIT80 Dimensions W x H x D 293 x 293 x 50mm Weight 0 8kg Long range prism 80KIT100 Dimensions W x H x D 394 x 394 x 5 mm Weigh...

Reviews: