background image

 

 

TFH-280A 

© 2010

 

 

2012 Telefire Fire & Gas Detectors Ltd 

 

Revision 1.01   January 2012 

 

– Page 4 of 4 – 

Indications and Troubleshooting 

The detector includes an indicating LED that flashes with every access from the control 
panel and is turned solid on during alarm. 
A detailed message will also be displayed on the control panel and remote annunciators. 
Please see the control panel’s manual for a detailed explanation of alarm, fault, and 
maintenance alarm indication. 

Specification 

Diameter ....................................................................... 101 mm including base 
Height (including base and LED)................................... 52 mm 
Weight .......................................................................... 106 gr. 
Operating Temperature Range ..................................... -10°C – +60°C (14°F – 140°F) 
Relative Humidity Range .............................................. 10% – 93% non-condensing 
Sensitivity Range (set at control panel) 

Rate of Rise Mode ................................................. 7°C – 13°C /minute or 60°C 
Fixed Temperature Mode ....................................... 50°C – 90°C in 1°C increments 

Operating Voltage 

(supplied by control panel via SLC) ........................ 21V, Modulated 

Maximum Current Consumption: 

Quiescence mode .................................................. 200µA 
Alarm mode (without Auxiliary Indicators) .............. 2.6mA 
Alarm mode (3 Auxiliary Indicators) ....................... 35mA 

Maximum Current to auxiliary indicators ....................... 50mA 
Local Indication 

Local red LED (light-emitting diode) and an auxiliary indicator 
output.  Use only Telefire’s TFL-1AN Auxiliary Indicator for Analog 
Addressable Conventional Detectors.  Connect up to 5 auxiliary 
indicators to each detector. 

All values are nominal.  Specifications are subject to change without prior notice 

Certification 

Telefire’s TFH-280A Analog Addressable Heat Detector has the following approvals: 

 

EN 54-5 Approved 

 

IS 1220 Approved 

 

GOST Approved 

 

UL 521 Compliant 

 

CE Marked 

 

Reviews: