background image

 

 

TFO-480A 

© 2010 –

 

2012 Telefire Fire & Gas Detectors Ltd 

 

Revision 1.01   January 2012 

 

– Page 2 of 5 – 

3.1 

Pre-Installation Planning 

3.1.1  Capacity Planning 

Ensure that the total number of initiating devices (detectors, switches, call point, etc.) 
does not exceed the maximum allowed per detection zone, floor area, or other 
limitations as specified by the applicable standards and regulations.  Ensure that the 
ADR-3000 has an available address for each detector. 

3.1.2  Cabling Planning 

The detector is connected to the control panel via a TFB-180 standard detector base via 
a two-wire connection (the control panel's SLC loop).  The detector has an output for 
activating a TFL-1AN Auxiliary Signaling Indicator for Analog Addressable Detectors.  It 
is recommended that you use a twisted pair cable for SLC connection.  Please look at 
the technical manuals of the TFB-180 and TFL-1AN for additional details about 
connecting the SLC cables and TFL-1AN to the base. 

   Note    

Notify the operator or the security personnel that the system will be temporary 
disconnected before adding detectors to the control panel. 

3.2 

Installation 

3.2.1  Address Programming 

Assign the TFO-480A’s address in the range of 1 – 127 prior to installation by using the 
PROG-4000 Analog Addressable Detector and Accessory Programmer.  Please refer to 
the PROG-4000 manual for additional details. 

3.2.2  ADR-3000 Configuration  

Configure the detector as “

Photoelectric Detector

” in the ADR-3000.  Configure the 

detector’s sensitivity at the control panel (“0.8” – most sensitive, “2.0” – least sensitive”) , 
if required. 
Please refer to the ADR-3000 technical manual for a detailed description of 
programming and configuration. 

3.2.3  Location 

The TFO-480A is designed to protect indoor fire risk areas, except environments where 
smoke, steam, dust, or corrosive gasses are present under normal conditions. 
Photoelectric smoke detectors should be used for detecting smoldering fires in corridors 
and along escape routes, wood- or paper stores, electric cabinets, etc., They should not 
be used in steamy, dusty, or smoky areas such as kitchens, bathrooms, saunas, 
laundries, etc. 
Observe NFPA 72 guidelines and local fire codes when installing the TFO-480A. 
When installing a TFO-480A smoke detector on a slanted (up to 45°) ceiling that allows 
free flow of smoke (i.e., there are no beams or other obstacles) the detector should be 
installed parallel to the flow line of the ceiling, and not horizontally.  For ceilings with 
impediments to free smoke flow please refer to the relevant local fire code standard. 
Use only Telefire's TFB-180 Standard Detector Base. 
For remote signaling use only Telefire's TFL-1NA Auxiliary Signaling Indicator for Analog 
Addressable Detectors. 

Summary of Contents for TFO-480A

Page 1: ...nical Manual TELEFIRE FIRE GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel 972 3 921 1955 Fax 972 3 921 1816 eMail marketing telefire co il Web www telefire co il TFO TFO TFO TFO 480A 480A...

Page 2: ...line UL 864 and UL 268 standards and Fault as used in EN 54 standards are used interchangeably throughout this manual i Note Do not install operate and maintain this product before fully reading this...

Page 3: ...smoke from burning of various materials Soft set address the detector s address is programmed into its memory without the use of mechanical switches or moving parts Can be tested directly with a test...

Page 4: ...ressable Detector and Accessory Programmer Please refer to the PROG 4000 manual for additional details 3 2 2 ADR 3000 Configuration Configure the detector as Photoelectric Detector in the ADR 3000 Con...

Page 5: ...see the control panel s technical manual for an explanation on performing Detectors Init i Note Ensure that detector initialization is performed when all detectors are in a smoke free condition 3 3 Po...

Page 6: ...detector is in alarm mode it keeps the alarm condition until reset by the control panel If the control panel is in Walk Test mode it will reset the alarm after a few seconds Please refer to the ADR 3...

Page 7: ...3 non condensing Sensitivity Range set at control panel 0 8 2 0 foot obscuration Operating Voltage supplied by control panel via SLC 21V Modulated Maximum Current Consumption Quiescence mode 290 A Ala...

Reviews: