TFO-480A 

© 2010 –

 

2012 Telefire Fire & Gas Detectors Ltd 

 

Revision 1.01   January 2012 

 

– Page 5 of 5 – 

Indications and Troubleshooting 

The detector includes an indicating LED that flashes with every access from the control 
panel and is turned solid on during alarm. 
A detailed message will also be displayed on the control panel and remote annunciators. 
Please see the control panel’s manual for a detailed explanation of alarm, fault, and 
maintenance alarm indication. 

Specification 

Diameter ....................................................................... 101 mm including base 
Height (including base and LED)................................... 52 mm 
Weight .......................................................................... 106 gr. 
Operating Temperature Range ..................................... -10°C – +60°C (14°F – 140°F) 
Relative Humidity Range .............................................. 10% – 93% non-condensing 
Sensitivity Range (set at control panel) ......................... 0.8 – 2.0%/foot obscuration 
Operating Voltage 

(supplied by control panel via SLC) ........................ 21V, Modulated 

Maximum Current Consumption: 

Quiescence mode .................................................. 290µA 
Alarm mode (without Auxiliary Indicators) .............. 2.6mA 
Alarm mode (3 Auxiliary Indicators) ....................... 35mA 

Maximum Current to auxiliary indicators ....................... 50mA 
Local Indication 

Local red LED (light-emitting diode) and an auxiliary indicator 
output.  Use only Telefire’s TFL-1AN Auxiliary Indicator for Analog 
Addressable Conventional Detectors.  Connect up to 5 auxiliary 
indicators to each detector. 

All values are nominal.  Specifications are subject to change without prior notice 

Certification 

Telefire’s TFO-480A Analog Addressable Photoelectric Smoke Detector has the 
following approvals: 

 

EN 54-7 Approved 

 

IS 1220 Approved 

 

GOST Approved 

 

UL 268 Compliant 

 

CE Marked 

 

Summary of Contents for TFO-480A

Page 1: ...nical Manual TELEFIRE FIRE GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel 972 3 921 1955 Fax 972 3 921 1816 eMail marketing telefire co il Web www telefire co il TFO TFO TFO TFO 480A 480A...

Page 2: ...line UL 864 and UL 268 standards and Fault as used in EN 54 standards are used interchangeably throughout this manual i Note Do not install operate and maintain this product before fully reading this...

Page 3: ...smoke from burning of various materials Soft set address the detector s address is programmed into its memory without the use of mechanical switches or moving parts Can be tested directly with a test...

Page 4: ...ressable Detector and Accessory Programmer Please refer to the PROG 4000 manual for additional details 3 2 2 ADR 3000 Configuration Configure the detector as Photoelectric Detector in the ADR 3000 Con...

Page 5: ...see the control panel s technical manual for an explanation on performing Detectors Init i Note Ensure that detector initialization is performed when all detectors are in a smoke free condition 3 3 Po...

Page 6: ...detector is in alarm mode it keeps the alarm condition until reset by the control panel If the control panel is in Walk Test mode it will reset the alarm after a few seconds Please refer to the ADR 3...

Page 7: ...3 non condensing Sensitivity Range set at control panel 0 8 2 0 foot obscuration Operating Voltage supplied by control panel via SLC 21V Modulated Maximum Current Consumption Quiescence mode 290 A Ala...

Reviews: