– Page 28 of 28 –
LED
Its Color and meaning
(EN 54 / CP 10 version)
Its Color and meaning (UL 864
/ IS 1220 version)
Telecom
Red/Yellow LED. Indicates a
fault event in the dialer line.
Additionally a fault alert marks
this event.
•
Off in normal operation
•
ON in red during dialing
•
Flashes in yellow when
there is a fault event in the
dialer
•
Solid yellow when the dialer
is disabled
Red/Yellow LED. Indicates a
fault event in the dialer line.
Additionally a fault alert marks
this event.
•
Off in normal operation
•
ON in red during dialing
•
Flashes in yellow when
there is a fault event in the
dialer. Pressing the
Acknowledge
key will turn
the LED on until the fault is
resolved
•
Solid yellow when the dialer
is disabled
Sounders
Red/Yellow LED. Indicates a
situation where the horns are
disabled due to a fault in the
horn line or disablement of the
horn output.
•
Off during normal operation
•
ON in red during horn
activation
•
Flashes in Yellow when
there is a fault in the horn
line
Red/Yellow LED. Indicates a
situation where the horns are
disabled due to a fault in the
horn line or disablement of the
horn output.
•
Off during normal operation
•
ON in red during horn
activation
•
Flashes in Yellow when
there is a fault in the horn
line. Pressing
Acknowledge
will turn the
LED ON until resolution of
the problem
•
Solid yellow when horn
output is disabled
Silenced
Yellow LED. Indicates silenced
condition.
•
Off during normal operation
and during alarm
•
Flashes during alarm after
silencing.
Yellow LED. Indicates silenced
condition.
•
Off during normal operation
and during alarm
•
Flashes during alarm after
silencing.
Test
Yellow LED. Indicates test
mode.
•
Off during normal operation,
•
On during Field Test.
Yellow LED. Indicates test
mode.
•
Off during normal operation,
•
On during Field Test.