Observe Batteries polarity. Wrong connection can cause damage to the ECD.
Connect AC input power.
Verify that the ECD is working properly; the alphanumeric display scrolls the character
8
from left to right and only the Power led is ON.
11.6
Post-Installation
11.6.1
Switching the Control Panel On
Activate the control panel and ensure that it is working properly (the digital display
moves the figure
8
from left to right and only the power led is on).
11.6.2
Configuring the Control Panel
The ECD is delivered in a default configuration.
Modify only if necessary, by programming the ECD, as explained in
Control Panel
Programming
, page 55
The time and date must be updated' the password has to be modified, etc
11.6.3
Setting the Date and Time
The TSA-1000 includes a real-time clock and calendar that are used for logging system
events. Ensure that you set the date and time after powering on (see section
15.7 on
page 66). The clock/calendar circuit includes a power backup for about five hours
without power sources – verify and set the time and date if the TSA-1000 was powered
off more than 5 hours.
11.6.4
Control Panel Programming
Program the control panel configuration and activation matrix. Chapter
0 on page 52
has detailed programming information.
11.6.5
Field Test
Perform a field test – this test allows a single operator to perform a test for all field
devices, including detectors, call points, and other inputs (see page 65 for instructions
for performing Field Test).
The testing process is automatic except for activation of the device which is done
manually by means specified by the device's manufacturer.
Telefire's devices can be tested by putting a magnet to the test point of the detectors or
activation of the call points through the testing tool (supplied with the call point).
11.6.6
Activation Test
Test the outputs of the system to ensure that they are activated according to the
conditions specified by the consultants.
11.6.7
Arming Extinguishing Devices
Ensure all input devices are in normal state and no devices are in alarm.
11.6.8
Change Password
It is recommended to change the operator password after completing the installation and
system testing. See section
15.6 on page 66 for explanation on changing passwords.