13.3
Extinguishant Quantities
•
It is possible to connect up to three, simultaneously activated solenoid-operated
containers to the TSA-1000. Additional containers may be activated with a delay of
at least 20 seconds between activations
•
It is possible to connect a single GCA-activated container to the TSA-1000 – this will
be connected only to output 1 (see
Figure 19)
•
It is possible to connect one GreenEX aerosol releasing device to each
programmable output on the TSA-1000
•
It is possible to connect one TLA-44 to each programmable output, as long as there
are no simultaneous activations. Multiple outputs may be activated with a delay of
at least 20 seconds between activations. Each TLA-44/1 module can activate a
single FirePro aerosol generator, while each TLA-44/4 module can activate up to 4
FirePro aerosol generators.
i
Note
Please consult the manufacturer for solutions regarding activations of
additional extinguishing devices
13.4
Fike FIRERASER
Fike's FIRERASER cylinders are suitable with work for all of Telefire control panels.
For additional detail, refer to Fike’s technical manual.
Figure 18 Connecting a FIRERASER Cylinder for Automatic Extinguishing