TSA-1000
© 2008
–
2012 Telefire Fire & Gas Detectors Ltd
Revision 1.12
האיגש
!
אצמנ אל הינפהה רוקמ
.
2
– Page 56 of 56 –
Key
Function in Programming Mode
▲
(2)
Navigates between options available in the selected field
▼
(3)
Navigates between options available in the selected field
Enter
(4)
Selects, marks or removes a zone from the matrix
Ack/Prog
(5)
Copies the temporary programming to the non-volatile memory
Reset
Exits programming mode without saving. The display shows
nSv
(not
Saved) and will return to programming mode after a few seconds.
Pressing the Reset key a second time will exit without saving.
14.4
Display During Programming
During programming the 3-digit 7 segment display represents:
•
Leftmost digit – device type
•
Middle digit – device (input, output, or relay) number
•
Right digit – mode of operation
Event type field (the top three LEDs to the right of the digital display) will indicate the
event type (alarm, fault or supervisory)
Delay field – represented by the six left LEDs and the bottom five LEDs on the right of
the general display area indicate delay time in steps of 5 seconds.
The
Alarm
LED indicates alarm verification for inputs and
Silenced
for outputs.
The zone indicators represent input zones for output matrix programming. During matrix
programming when the alarm zone LED is lit, it means that activating this zone will
cause an alarm condition. During matrix programming when the supervisory zone LED
is lit, it means that activating this zone will cause a supervisory fault condition.
Selected fields blink when selected.