Press the
Menu
key to move the cursor to select verification for input devices or
silenced for output devices (Alarm LED) or delay
•
Press the
Menu
key to move the cursor to select the input zones for the matrix
(alarm LED of the in the zone display area)
Figure 25 Device selection
14.6
Dialer Programming
The dialer's operating function is fixed – the display shows
d1G
(dialer output is general
output).
14.7
Horn Output Programming
The horn's operating function is fixed except for the requirement of CP-10 (see below) –
the display shows
H1G
(dialer output is general output).
CP 10
CP 10 Requirement
CP-10 specifies that in some cases the horn output may not be silenced for 3
minutes after alarm. To set this requirement press
Menu
until the third digit
(
G
) will blink and use the
▲
or
▼
keys until the dot will show (feature enabled
–
H1G.
, feature disabled –
H1G
).
When enabling this feature, paste a label stating "
Bell silence is disabled
for a period of 3 minutes upon first alarm
" on the front door of the panel.
14.8
Expansion Card Programming
During expansion card programming the left digit will be
C
(expansion
C
ard). The
middle digit represents the card number (
1
– first expansion module,
2
– second module,
etc). Do not skip card numbers (i.e., do not program card 2 if you do not have card 1
installed). The right digit will show the card type:
•
0
– not installed
•
1
– TSA-1000E8 (8 zones)