Figure 28 Display during input programming
CP 10
CP 10 Requirement
CP-10:2005 section 2.5.11 states "the following components shall not be
subject to alarm verification feature:
(a) Alarm zone facilities containing only manual call points
(b) Circuits between sub alarm panels and the main alarm panel
(c) Detectors used to activate fire suppression systems
(d) Detectors installed in high-risk areas
(e) Alarm zone circuits from fire suppression systems".
IS 1220
IS 1220 Requirement
IS 1220 Part 3 does not allow delaying zones that are a part of cross-zone
activation; zones that have heat detectors; and zones that have call points.
14.13 Output Programming
All the system's outputs are programmable and can be configured as either alarm or
supervisory outputs.
The main board contains 4 outputs, numbered 1 – 4 from left to right. Outputs on the
expansion modules are indicated by a LED next to the output's contacts on the
expansion card that is lit when selected.
During output programming the left digit will be
o
(
o
utput). The middle digit represents
the output number (
1.
– first output,
2.
– second output, etc). The rightmost digit
represents the output's operating mode (
G
– General;
A
– logical "And" of selected
inputs,
b
– logical "Or" of selected inputs;
E
–
E
xtinguishing output).