14.13.1 Additional Parameters for General Outputs
An output that is defined as a General output can be programmed as an Alarm output or
Supervisory output using the LEDs to the right of the digital display.
When selecting an alarm output we have additional fields to define, the delay field,
"silenced" field, and the matrix field.
•
General Alarm outputs can be programmed with a delay, and defined as "silenced"
or "not silenced".
•
General Supervisory outputs can be programmed with a delay.
Refer to section
14.5 on page 57 for a detailed explanation of these fields.
CP 10
CP 10 Requirement
CP-10:2005 section 2.5.8 states "no isolation and delay facilities shall be
allowed for the transmission of fire alarm signals to fire alarm sounders".
Programmable outputs that are defined as "silenced" are considered as fire
alarm sounder outputs and can not be disabled.
14.13.2 Additional Parameters for Logical "And" Outputs
An output that is defined as a Logical "And" output can be programmed as an Alarm or
Supervisory output using the LEDs to the right of the digital display.
•
Logical "And" Alarm outputs can be programmed with a delay, defined as "silenced"
or "not silenced", and the zones that belong to the logical operation.
•
Logical "And" Supervisory outputs can be programmed with a delay, and the zones
that belong to the logical operation.
Refer to section
14.5 on page 57 for a detailed explanation of these fields.
UL 864
UL Requirement
•
UL 864 Edition 9 does not allow input zone delay in conjuncture with cross-
zoning.
•
UL 864 states that when utilizing more than one zone with verification, the
max verification time shall not exceed 30 seconds