Operation and Maintenance
15.1
Evacuation (EVC)
Press the
Menu
key to enter the main menu. Press the
▲
or
▼
keys until the display
shows
EVC
. Press the
Enter
key to activate all general outputs.
In a networked system the digital display will alternately display
EVC
and the panel
number that has activated the evacuation (
P##
).
15.2
On / Off Zone or Output (OFF)
Press the
Menu
key to enter the main menu. Press the
▲
or
▼
keys until the display
shows
OFF
. Press the
Enter
key to move the cursor to the device field. Select the
device by pressing the
▲
or
▼
keys. Press the
Enter
key to toggle the device between
normal and disabled. A disabled device will show
u
in the right digit.
Press the
Ack/Prog
key for a few seconds until the display will show
PPP
and a long
beep will sound. The system will indicate the disabled zone or output on the digital
display (
x#
u
), the
Disabled
LED in the general display area, and the disabled zone's
Disabled
LED in the zone display area,
15.2.1
Keyboard Locking
Keyboard locking prevents system configuration modification by unauthorized personnel,
when the system's keyboard is locked there is no possibility to perform any functions
other than acknowledge an event, paging through memory to display alarm and fault
events.
The system's default configuration is locked keyboard.
When the keyboard is locked the system requests a password to perform any operation.
The system will return to locked keyboard automatically 30 minutes after the last key
press in unlocked condition.
Press the
Enter
key to toggle between locked (
bu
L
–
bu
ttons
L
ocked) and unlocked (
bu
)
keyboard
i
Note
Lock the keyboard after programming or maintaining the system.
15.3
Field Test (ft)
Field test is used for periodic testing of the system by a single person. Field test can be
selected for a single zone or a group of zones.
During field test activation of a device in the selected zones will light the device's alarm
LED, indicate the zone on the control panel by the zone number and alarm LED in the
digital display section. The test will not activate output devices. The system will reset
the activated zone about 15 seconds after activation. An alarm from a zone that was not
selected for testing will immediately activate the fire alarm condition on the panel.
Press the
Menu
key to enter the main menu. Press the
▲
or
▼
keys until the display
shows
Ft
. Press the
Enter
key. Select the zones for testing by using the
▲
or
▼
keys.
Press Enter to select the appropriate zone – the rightmost digit will show
t
. Press the
Ack/Prog
key to start the field test. The system will indicate Field Test mode by
displaying the Test LED in the general display area, the private Test LED in the zone
display area, and
– – –
on the digital display.