– Page 67 of 67 –
To exit without modifying the time and date press the
Reset
key, the system will display
nSv
(
n
ot
S
a
v
ed). This message will be displayed only when performing changes.
Pressing the
Reset
key a second time will exit without any changes.
15.8
Lamp Test (lt)
Page through the menus until the display shows
lt
.
Lamp test turns on all LEDs on the panel's keyboard / display and the digital display
shows
8.8.8.
. The internal buzzer will also sound. The two dual color LEDs (
Telecom
and
Sounders
) in the general display area will be yellow and then red.
15.9
Additional Information (inF)
The additional information menu shows the system's software version, and total number
of times the system was programmed.
15.10 Restoring Default Configuration (dEF)
This option allows the return to factory default (
dEF
).
The system requests you to enter the password twice in order to safeguard against
accidental reconfiguration.
15.10.1 Default Configuration
Relays 1 and 2 General Alarm Relay
Relay 3 General Fault Relay
All Inputs
Detector zone, unverified
All Programmable Outputs General Alarm, Silenced, no delay
Expansion Modules Not configured (TSA-1000/4)
Remote Annunciators Not configured
!
Warning
All system configuration and programming (including passwords,
activation conditions and matrices) are set back to the factory default
values.
Disconnect all extinguishing devices and other critical activation
outputs before returning to factory default. Reconfigure the panel for
the site's specific requirements and ensure that all input devices are in
normal state and not in alarm and that the activation matrices are
properly configured before reconnecting any extinguishers.