TSA-1000
© 2008
–
2012 Telefire Fire & Gas Detectors Ltd
Revision 1.12
האיגש
!
אצמנ אל הינפהה רוקמ
.
2
– Page 69 of 69 –
H
–
Open wire on Horn output
H
u
Horn output disabled
H
י
Short wire on Horn output
V
d
24Vdc fault
V
r
24Vdc (resettable) fault
#
#
'
Short wire on zone #
#
#
–
Open wire on zone #
#
#
Ξ
A pressostat input (
Ξ
) input was activated on input ##
#
#.
'
Short wire on programmable output #
#
#.
–
Open wire on programmable output #
#
#.
|
Over–current on output ##
2
4
i
Faulty 24V supply from the power supply
A
#
'
Annunciator # is disconnected
A
#
A
Annunciator # is connected, but is not configured
b
t
–
Disconnected battery
b
t
L
Low battery voltage
C
#
–
Expansion Module # is not connected
C
#
c
Expansion module # – configuration error
C
#
E
Expansion Module # is connected, but is not configured
C
h
–
Charger fault (disconnected)
C
H
L
Low charge
C
h
י
Charger fault (short)
C
o
d
Checksum error – return the TSA–1000 to the manufacturer for
repair
C
P
r
Hardware reset (CP 10 version only)
d
A
t
Checksum error on site–specific data. Return the control panel
to the factory default configuration (see section
15.10.1
15.10 on
page 67). Reconfigure the control panel, including input,
outputs, and activation matrices.
d
t
'
FWRE output is shorted
d
t
–
FWRE output is open
E
#.
A
Extinguishing output # activated.
This display remains even after control panel reset to
ensure replacement of extinguishing agent. To clear this
status enter programming mode and return to normal after
a few seconds.