TSA-1000
© 2008
–
2012 Telefire Fire & Gas Detectors Ltd
Revision 1.12
האיגש
!
אצמנ אל הינפהה רוקמ
.
2
– Page 70 of 70 –
E
E
P
EPROM failure – return to manufacturer for repair
G
F
–
Ground fault – negative wire leakage
G
F
┤
Ground fault – positive wire leakage
i
Note
Ground leakage faults may affect output fault display. Resolve the ground
fault issues first.
16.4
Programming Faults
#
E
Extra Device – a control panel exists in the network but is not
defined as a Sub Panel
E
r
r
Wrong password
E
0
1
Expansion module configuration error
E
0
2
The expansion module that is installed is not the type that was
configured
E
2
0
Zone definition error
E
2
1
Non-consecutive zone number (e.g., an expansion module was
configured as zones 6 – 13 instead of 5 – 12)
E
4
0
An output was defined as neither an alarm nor a supervisory
output
E
4
1
An extinguishing output was defined as a supervisory output
E
4
2
A supervisory output is defined without supervisory inputs
E
4
3
Output configuration error
E
4
4
Non-consecutive output number (e.g., an expansion module
was configured as outputs 6 – 13 instead of 5 – 12)
E
4
5
A supervisory matrix configuration error:
•
A supervisory output matrix includes alarm or trouble inputs
•
A supervisory output has no supervisory inputs
•
An "And" (A) supervisory output has less than 2 inputs
•
An Or (b) supervisory output does not include any inputs
E
4
6
An alarm or extinguishing matrix configuration error:
•
An alarm output matrix includes supervisory or trouble
inputs
•
An extinguishing output matrix includes trouble inputs
•
An alarm or extinguishing output has no alarm inputs
•
An "And" (A) alarm output has less than 2 inputs
•
An Or (b) alarm output does not include any alarm inputs