Routine Testing
The TSA-1000 shall be tested weekly as specified in the next paragraph.
The system should be fully tested at least twice a year, or as required by national and/or
local fire codes. All devices, system wiring and component functions should be tested
and maintained. These inspections should be performed in addition to the routine
maintenance activities such as cleaning the detectors (which should be performed in
accordance with Telefire’s instructions).
Perform a Field Test of each zone.
Maintenance and test actions shall be conducted by a company or service technician
authorized by Telefire.
Records of all inspection and maintenance activities should be kept.
i
Note
Testing shall be performed by authorized service personnel that are
employed by authorized companies.
19.1
Weekly Inspection – To Be Performed by Site Personnel
The site's safety supervisor should inspect the control panel weekly and verify that all of
the following conditions exist:
•
The green LED is on and is not blinking
•
None of the yellow or red LEDs are on or blinking
•
The control panel's fault buzzer does not sound
•
The digital display moves the figure
8
from left to right
Call your service representative if any of these conditions is not met