TSA-200 / TSA-200XT / TSA-240 / TSA-240XT
© 2010 –
2014 Telefire Fire & Gas Detectors Ltd
Revision 1.06 July 2014
– Page 1 of 53 –
1
Introduction
Telefire's new generation conventional Control and Indicating Equipment (CIE, also
termed Fire Alarm Control Panel, FACP, or Fire Detection and Alarm System, FDAS)
narrows the gap between analog and conventional systems. Drawing on over three
decades' of experience in designing and manufacturing fire alarm Control and Indicating
Equipment (CIE), the state of the art TSA-200 / TSA-200XT / TSA-240 / TSA-240XT
Conventional Two- and Four-Zone Fire Alarm Control and Indicating Equipment (CIE) is
certified to EN 54-2 and EN 54-4; is CE marked, is certified to GOST 53325-2009 and
complies with UL 864 Edition 9.
The TSA-200 product family is ideally suited for new and retrofit applications. The base
Control and Indicating Equipment (CIE, or Control Panel, CP) supports two or four
zones, a horn output, an Alarm dialer output, a Fault Dialer Output and two relays. The
system supports maintenance alert and drift compensation for detectors (dependant on
using Telefire detectors), a function that required, until now, analog addressable panels.
Walk test mode allows for detector testing by only one technician, whilst discriminating
between triggers caused by the "test" process and actual alarms.
The system supports alarm dependency on more than one alarm signal (an alarm
verification feature, or AVF-Alarm Verification Function) to increase system reliability and
reduce nuisance alarms.
The TSA-200 can be converted into the TSA-200XT, a Fire Alarm and Extinguishing
control panel, by adding the EM1 Extinguishing Expansion Module.
The display logic of the TSA-200/TSA-200XT is that of UL,
(i.e. events cause LEDs to flash until the events are acknowledged)
making the TSA-200/TSA-200XT human interface UL864 compliant, as well as EN 54-2
and EN 54-4 certified.
The (original) EM1 card has two level activation outputs, using bipolar transistors.
The EM1 Rev. 1.1 is modified so output 3 is change polarity, and output 4 is Level
Activation. Both outputs use FETs.
i
Note
If an EN 12094-1 certified CDE (Electrical Automatic Control and Delay
Equipment) is required, please consult Telefire Fire and Gas Detectors Ltd.
regarding the TSA-200X, TSA-1000X and other products.