TSA-200 / TSA-200XT / TSA-240 / TSA-240XT
© 2010 –
2014 Telefire Fire & Gas Detectors Ltd
Revision 1.06 July 2014
Page 36 of 79
Shown below is a table of the of equipment and the number and type of relevant
adapter:
i
Note
When adapters are installed, addition of EOL resistors is not required!
i
Note
Please consult the manufacturer for solutions regarding activation of
additional extinguishing devices.
11.4
Type and Number of Extinguishing Adapters
Extinguishing Device
Maximal number of extinguishing adapters
SAFE solenoid gas
cylinders
A single TLA-110 adaptor connected to the extinguishing
output
FIKE solenoid gas
cylinders (FIRERASER)
A single TLA-130 adaptor connected to the extinguishing
output
FIKE GCA gas cylinders
A single TLA-22 adaptor connected to the extinguishing
output
FirePro aerosol generators A single TLA-44/1 or TLA-44/4 adaptor connected to the
extinguishing output
GreenEX aerosol
generators
A single TLA-33 adaptor connected to the extinguishing
output
i
Note
Connect a single extinguishing adaptor to the extinguishing activation output.
This adaptor will activate a single extinguishing device, except for the TLA-
44/4 that can activate up to 4 FirePro aerosol extinguishers.
Please consult Telefire Ltd. for solutions regarding activations of additional
extinguishing devices
11.5
Gas Extinguishing – SAFE Solenoid-Operated Gas
Cylinders
The TSA-200XT / TSA-240XT can activate a SAFE solenoid-operated gas cylinder via a
TLA-110 extinguishing adapter