TSA-200 / TSA-200XT / TSA-240 / TSA-240XT
© 2010 –
2014 Telefire Fire & Gas Detectors Ltd
Revision 1.06 July 2014
Page 48 of 79
LED
Its Color and meaning during normal operation
Activated
Red LED.
•
If extinguishing delay is programmed ON, the LED flashes
during extinguishing delay count-down (Pre Discharge
Warning Time).
•
ON during the extinguisher pulse duration period, OFF
when the extinguishing pulse ends.
Fault
Yellow LED.
•
Flashes when there is a fault in any of the extinguishing
module's inputs or outputs, changes to ON when
acknowledged, and stays ON until the faults are resolved
and Reset is performed. A dedicated LED next to the input
or output TB in the EM1 extinguishing module is also ON.
•
Flashes after the extinguishing pulse ended to indicate that
there is a need to refill or replace the extinguisher media
container. The General Fault LED flashes also. Can be
switched OFF by entering and exiting the programming
mode.