HVAC Daikin Non-VRV — on L1
For Daikin Non-VRV equipment, DC voltage supply
by TDS20065 might be
required for proper
operation.
Before enabling DC output from TDS20065 make sure
there is no DC voltage on HVAC communication line.
1
Measure DC voltage on HVAC communication
line L1
2
If no DC voltage
.
Daikin 14-16V DC
change
the dip switches
as shown below
3
Turn ON the power
for TDS20065 and
connect
it to HVAC line.
4
Connect to the communication terminals on
the HVAC equipment and secure the cables in
the L1 line plug.
5
Insert the plug in to the TDS20065 L1
socket.
Daikin Non-VRV HVAC Terminal
Changing the dip switches
, while DC voltage is present on L1,
may damage
the TDS20065.
L1
2
1
4
3
5
Summary of Contents for TDS20065
Page 1: ...TDS20065 Quick Installation Guide...
Page 27: ...40 Mounting on a wall...