SIMPO - BASIC INFORMATION
Page 2 of 48
Simpo Addressable Panel
Addressable Fire alarm Panel: Simpo
1.) Technical specification
Loops:
• Up to 2 – both built in the main PCB. The second is with additional PCB mounted
over the main PCB (on special terminals).
• Earth fault detection – enabling and disabling from the panel (Software).
Number of devices per Loop:
• Up to 250 devices (Series SensoIRIS)
with Teletek-Electronics protocol of
communication.
• Maximum devices per system: 500 with Teletek-Electronics protocol.
Zones:
• Up to 16 zones for the system.
• 16 zones with LED indication on the front panel.
Zone Groups:
• Up to 16 zone groups.
LEDs:
• 16 LEDs for Zone indication
• 14 LEDs for System Indication
Buttons:
• 6 navigation buttons – Enter, ESC, Up Arrow, Down Arrow, Left Arrow and Right
Arrow.
• 4 fast menu buttons – labeled 1, 2, 3 and 4.
• 4 system buttons for the fire alarm part – Silence Buzzer, Silence Alarm,
Evacuation and Reset.
Audible Indication:
• Built in buzzer.
Display:
• Monochromatic LCD display with 4 rows of 40 characters.
• Backlight.
Access Levels:
• 4 Access levels – 1 User, 2 Maintenance, 3 Programming and 4 Software update
• Switching between levels 1 and 2 from the front panel by means of 4 digits code
for access.
• Switching between levels 2 and 3 from the front panel by means of 4 digits code
for access.