IRIS/SIMPO Repeater TFT - Addressable Fire Alarm Repeater Panel
– Installation & Programming Manual
12
4.2. Programming Menus
To enter the Programming menus, press SYSTEM (
) button from Main Screen:
Press PROGRAMMING menu button. The following menus are available for settings.
Quick summery for the submenus:
- Setting Repeater Panel parameters
- Restore to factory default settings
- Save the Repeater system configuration
4.2.1. Panel Settings
In the PANEL submenu, the Installer sets a list with the most important parameters for the operation of the Repeater
panel.
Press PANEL menu button.
Quick summery for the submenus:
- Access Codes for Users and Levels
- Network settings for the Repeater
- Disable/Enable the internal buzzer
- Change the Language
- Set Company Information (Screen Saver)
4.2.1.1. Setting Access Codes and Levels for Operation
There are three access levels for control in Repeater panel with different functionalities and rights for operation. Four
access codes can be set with different access level for users.
The default code combinations (factory set) with set access levels are presented in the following table.
Access
Level
Description
Factory
Code
Access and Functionalities
1
User
0000
1111
Only
Silence buzzer
and
Evacuate*
buttons are active. It is not allowed to enter
Maintenance and Programming access levels.
* Just for those cases, when there is active fire alarm signal, received from a loop device.
2
Maintenance
2222
Silence buzzer, Silence sounders, Reset
and
Evacuate
buttons are active.
Maintenance access level entry, which allows partial programming and menu
settings.
3
Installer
3333
Silence buzzer, Silence sounders, Reset
and
Evacuate
buttons are active.
Installer access level entry, which allows full programming and settings.