IRIS/SIMPO Repeater TFT - Addressable Fire Alarm Repeater Panel
– Installation & Programming Manual
13
Enter SYSTEM - PROGRAMMING
– PANEL – ACCESS CODES menu.
Fields description:
•
Access Code Number
–
Use the left/right buttons to
change the code number. Up to 4 code numbers are
available for operation.
•
Access Code
– Active button for changing the set
code combination.
•
Access Code Level
– Active button for changing the
access level of the set code number.
To change the code combination, press the active digit button next to ACCESS CODE field.
Enter new 4-digits code combination into the text field.
Press OK.
Enter again the same code to verify it. Press OK.
The following messages inform for errors during verifying
the access code:
“Wrong Code”
– The second entered code combination
does not much with the first one.
“Text”
– Less than 4 digits are entered in the field.
In case the new code is valid and correctly verified, the
Repeater returns to ACCESS CODE menu showing the
new code set into the Access Code active digits button.
Press APPLY button to save the change.
To change the Access Level, press the active digit button next to ACCESS CODE LEVEL field. Every pressing of the
button increases the number in the field. The Access Levels are described in the table above.
Attention: There must be at least one code in the system with an access code level 3! It is not allowed to
edit a level of access (3) if it is the only one!
Press APPLY button to save all introduced changes.
Auto Log Off
– Option for automatic logging out from the
current set Access Level 2 or 3 after a time period and no
operation with the Repeater. If the automatic log out is
enabled, the Repeater will log out to Access Level 1 when
the programmed time is over.
The option is Disabled by default
. Every pressing of
Disabled/Enabled button changes the setting.
The time period is set in minutes from 1 to 60 (30 minutes
by default). To change it, press the active digits button
and enter new time period - see item