IRIS/SIMPO Repeater TFT - Addressable Fire Alarm Repeater Panel
– Installation & Programming Manual
16
Examples for settings in PANELS submenu.
The receiving of messages for events is Enabled. The
options for repeating the outputs status are available for
further settings. Every pressing of the button will change
the status Enabled/Disabled.
Press APPLY button to save all introduced changes.
The receiving of messages for events is Disabled. The
options for repeating the outputs status are unavailable
for settings.
Even if there are options set as Enabled, they
will be inactive and the panel will not repeat the status of
any of the outputs.
Press EXIT button to move back to previous screen.
Examples for status in PANELS submenu.
New panel number is found in the network configuration.
Press ADD button. The status will change to PRESENT. If
there is set name for this panel it will be displayed into the
text field.
Next step is to Enable the “Receiving” and
“Sending” control commands to other panels. Confirm with
APPLY button to save the settings.
The screen displays the information for the Repeater
panel
– status THIS. No other settings for
Receiving/Sending commands or messages are
available.
Remember, the Receiving/Sending commands
and messages for events for the Repeater itself can be
done only via the other connected panels in the network.
IMPORTANT NOTES!
The main purpose of the Repeater panel is presenting remote indication of fire alarm, fault, trouble, warning and other
type of events, reported from other fire alarm panels (IRIS and SIMPO series) or repeater panels connected into one
common network.
In case of making software or hardware Restore Defaults, the Repeater will restore the factory default settings
,
including the Network Settings:
•
The Panel Number of the Repeater at Network Settings submenu is set by default as 1 - the installer must set
the real number of the Repeater in the network before enabling it
– see item
•
All connected panels will be recognised as NEW and must be added manually one-by-one in the PANELS
submenu of the Repeater.
•
The options for Receiving/Sending control commands and receiving/repeating of messages for events are
Disabled
– the installer must enable all of them to restore the reporting from the other panels in the network
and the remote indication in case of events
•
The Repeater panel must be deleted from the rest panels in the network and ADDED again after all settings
are completed.
It is recommended, before making a Restore Defaults of the Repeater, to save its current system configuration
as TDF file using ProsTE specialized programming software.
After software or hardware resetting, load the TDF
back to the Repeater and save time for introduce settings in menus. For details about ProsTE specialized programming
software ask your local distributer of the equipment.