IRIS/SIMPO Repeater TFT - Addressable Fire Alarm Repeater Panel
– Installation & Programming Manual
7
2.2. Initial Power-up
When turned on, the Repeater panel always conducts a procedure of loading the parameters, which usually takes about
30 sec. A long sound signal is heard. There is no access to the menus of the Repeater panel during that procedure.
Access Level 1 is loaded. Upon the initial start-up, the Repeater does not hold any configurations.
Next, the installer has to perform settings for the network and the parameters of the Repeater as described at item
2.3. Sound Signalization
The IRIS/SIMPO Repeater panel is equipped with internal buzzer for sound signalization in case of events.
Signalization
Description
Button
Single short beep indicating the pressing of a button.
Reset or Event
Single long beep indicating reset of the Repeater or receiving of message for Disable, Test or
Warning event.
Technical trouble
Short beeps in case of receiving of messages for Fault event (for the Repeater itself or for other fire
alarm panels in the network). The beeps can be stopped from Access Level 2 and 3 after
performing Silencing Buzzer from the Main Screen menu.
The beeps will stop when the technical trouble is restored and the fault event is cleared
automatically from the Faults list.
Fire Alarm
Continuous sound signal for activated Fire Alarm from zone or Evacuation. The sound can be
stopped from Access Level 2 and 3 after performing Silencing Buzzer from the Main Screen menu.
3. ELECTRICAL CONNECTIONS
3.1. PCB Elements
Attention: Do not remove the PCB from the box bottom!
Figure 7
1
– Main power supply terminal. See item
2
– RS485 interface. Used for realizing network with other panels via RS485 communication
protocol. See item
3
– LED Indication for the status of the network via RS485 interface. See item
4
– LAN interface connector. See item
5
– Micro USB port for software and firmware update. See also item
6
– Jumper for hardware restore defaults. See item
7
– Built-in 3V backup battery for the real-time clock and jumper BTR for battery activation. The
jumper BTR is factory set and must not be removed.
8
–
Built-in sound buzzer (on the back side of the PCB).
TFT Touch Screen