IRIS/SIMPO Repeater TFT - Addressable Fire Alarm Repeater Panel
– Installation & Programming Manual
9
The maximum cable length between two network modules and/ or repeater panel is 1000m.
Figure 9
Up to 64 panels can be connected in a common redundant network.
Figure 10
3.4. LAN Network
The realization of LAN network is possible only for Repeaters and other iRIS8 addressable fire alarm panels (up to 64).
The LAN connection can be direct panel-to-panel or by means of a HUB via TCP/IP protocol.
Note: The LAN connector is accessible after removing the left and right side covers and the front panel of the enclosure
box
In installer’s menu (Access Level 3) enter SYSTEM – PROGRAMMING – PANEL – NETWORK – NETWORK
SETTINGS, and set for Network type option “LAN” – see item
3.5. Hardware Restore Defaults
This is an option for restoring the factory set parameters of the Repeater panel.
It is recommended, before making a Restore Defaults of the Repeater, to save its current system configuration
as TDF file using ProsTE specialized programming software.
After hardware resetting, load the TDF back to the
Repeater and save time for introduce settings in menus. For details about ProsTE specialized programming software
ask your local distributer of the equipment.
To perform hardware, restore defaults do as follows:
1. Turn off the main and backup power supply of the Repeater panel.
2. Remove the right side cover as shown on Figure 3.
3. Put a jumper on Restore Defaults terminals on the PCB of the Repeater
– Figure 7, position 6.
4. Turn on the main and backup power supply of the Repeater. A long sound signal is heard. The screen enters into
procedure for hardware calibration of the display. Perform the calibration as follow the detailed description how to do
that in item
5. Remove the Restore Defaults jumper.
6. Close the right side cover of the enclosure box.
Maximum 64 panels
iRIS8 Fire panel
SIMPO Fire panel
Repeater TFT
Redundant network
Module 1
Redundant network
Module 2
iRIS8 Fire panel
iRIS8 Fire panel
SIMPO
Fire panel
Repeater TFT
Power
supply
24V DC
Redundant
Module
Redundant
Module
Redundant