57
Remote monitoring
:
In this section you can configure the Contact ID event code for reporting to CMS and can select
the preconfigured notification template for the given event. The Contact ID event code should only
be configured if reporting to CMS is used, otherwise select the notification template named
“
EMPTY
”.
Event code
: in this section you can configure the 3-digit Contact ID event code, consisting of
characters 0...9,A,B,C,D,E,F, which you wish to assign to the given event. The default event codes
are configured according to the standard list of Contact ID event codes.
Partition
: in this section you can configure the partition number which you want to assign to the
given event. The default configuration for partition is 01, except for error events.
Zone
: in this section you can configure the zone number which you want to assign to the given
event.
Notification template
: in this section you can select a preconfigured notification template which
you want to use for the given event. If you want to use additional notification templates, these
should be added prior to configuring the events. If you do not want to send a report to CMS on the
given event, select the template named “
EMPTY
”.
Output
:
In this section you can configure the output(s) to be controlled upon occurrence of the given
service event.
Output control mode
: in this section you can configure the control mode of the output (or the
selected output 1 or 2 in case of the IN4.R2 model). Available options:
None
: the output will not be used.
Monostable
: the output will be activated for the time configured in the
“Duration”
section
of the output parameter settings, then it will revert to normal state automatically.
The duration can be configured from 5 milliseconds to 60 minutes.
Bistable ON
: the output will be activated permanently and will change state only upon
receiving a different command or upon power loss.
Bistable OFF
: the output will become deactivated.
State change
: the output will change state (if deactivated, it will become activated and if
activated, it will become deactivated).
Pulse series
: the output can be controlled by pulse series as well. The number of pulse
series can be configured from 1 up to 3. For each pulse it can be configured how long the
output should be activated, how long should be deactivated, the number of repetitions and
the pause between repetitions. The active periods can be configured from 5 milliseconds to
60 minutes and the number of repetitions can be configured from 1 to 10, and the pause
between pulses can be configured from 5 milliseconds to 60 minutes too.
Output parameter settings
: this option becomes available if an output control mode is selected
which has further settings. In this section you can configure the additional settings of specific
output control modes, such as timings for monostable control and pulse series. Click on the “
Edit
”
button to open the parameter configuration window.