9
2.4.2 Wiring of Pager 7 Z6
System terminal inputs and outputs:
V+:
Supply voltage 9-30V DC (min. 500 mA)
V-:
Supply voltage negative polarity
IN1:
1. contact input
IN2:
2. contact input
IN3:
3. contact input
IN4:
4. contact input
IN5:
5. contact input
IN6:
6. contact input
OUT1:
1. normally open relay contact
In our example IN1, IN2 and IN3 inputs are normally open
(NO), IN4 and IN5 inputs are normally closed (NC), while
IN6 input is a temperature sensor (easyTemp).
2.5 SIM card related information
2.5.1 Selecting services
To select which services to activate on the SIM card, you need to know what features of Pager
7 you’d like to use in practice.
Several features of Pager 7 require having a mobile internet connection. A few of these features
are remote programming, remote firmware update, reporting to a monitoring station and certain
notification options like e-mail sending. In case the SIM card has no mobile internet service the
module can be programmed only through USB connection and it can send only SMS or call
notification.
To use the internet service, you need to enter the SIM card’s Access Point Name (APN) in the
programming software. You can obtain
the SIM card’s public APN from your GSM provider.
APN settings are explained in detail in section 4.1.1 of this manual.
The functions that use SMS sending need SMS service and the ones that use calls require
GSM voice call service.